Calibrate the ControlLogix Analog I/O Modules Chapter 11
A Results wizard displays the status of each channel after calibrating for
a high reference. If channels are OK, continue. If any channels report an
error, retry steps
13
…
until the status is OK.
After you have completed both low and high reference calibration, this
window shows the status of both.
17.
Click Finish.