Calibrate the ControlLogix Analog I/O Modules Chapter 11

A Results wizard displays the status of each channel after calibrating for
a high reference. If channels are OK, continue. If any channels report an
error, retry steps

13

16

until the status is OK.

After you have completed both low and high reference calibration, this
window shows the status of both.

17.

Click Finish.