Rockwell Automation 1756-XXXX ControlLogix Analog I/O Modules User Manual

Page 224

Advertising
background image

224

Publication 1756-UM009C-EN-P - December 2010

Chapter 10 Configure ControlLogix Analog I/O Modules

2.

After the channels are configured, do one of the following:

• Click Apply to store a change but stay on the dialog box to choose

another tab.

• Click OK to apply the change and close the dialog box.

• Click Cancel to close the dialog box without applying changes.

Latch Limit Alarms

Check the box to latch an alarm if the
controller data value exceeds the
clamping limit.

See

page 170

in

Chapter 8

for details.

Latch Rate Alarm

Check the box to latch an alarm if the
output single changes at a rate that
exceeds the ramping limit.

See

page 169

in

Chapter 8

for details.

IMPORTANT

Clamping is only available in floating point mode.

Clamp values are in engineering scaling units and are not
automatically updated when the engineering high and low
scaling units are changed. Failure to update the clamp
values may generate a very small output signal that could
be misinterpreted as a hardware problem.