Rockwell Automation 1756-XXXX ControlLogix Analog I/O Modules User Manual

Page 72

Advertising
background image

72

Publication 1756-UM0009C-EN-P - December 2010

Chapter 4 Non-isolated Analog Voltage/Current Input Modules (1756-IF16, 1756-IF8)

1756-IF16 Single-ended Current Wiring Example

+

-

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

IN-0

IN-10

IN-1

IN-9

IN-2

IN-8

IN-5

IN-3

IN-6

RTN

IN-7

IN-4

IN-13

IN-12

IN-14

IN-11

RTN

i RTN-0

i RTN-7

i RTN-4

i RTN-6

i RTN-8

i RTN-9

i RTN-10
i RTN-11
RTN
i RTN-12
i RTN-13

RTN

i RTN-5

i RTN-1
i RTN-2
i RTN-3

IN-15

i RTN-14
i RTN-15

i

i

A

NOTES:

1. All terminals marked RTN are connected internally.

2. For current applications, all terminals marked iRTN must be wired to terminals marked RTN.

3. A 249

Ω

current loop resistor is located between IN-x and i RTN-x terminals.

4. Place additional loop devices (strip chart recorders, so forth) at the A location in the current loop.

5. Do not connect more than two wires to any single terminal.

40914-M

Jumper Wires

2-Wire
Transmitter

Shield Ground

User-provided
Loop Power