Rockwell Automation 1756-XXXX ControlLogix Analog I/O Modules User Manual

Page 281

Advertising
background image

Publication 1756-UM009C-EN-P - December 2010

281

Analog I/O Module Specifications Appendix A

Open circuit detection time

Zero reading within 5 s

Overvoltage protection, max

30V AC/DC with PTC and sense resistor

Normal mode noise rejection

60 dB @ 60 Hz

(1)

Common mode noise rejection

120 dB @ 60 Hz
100 dB @ 50 Hz

Channel bandwidth

3…262 Hz (-3 dB)

(1)

Settling time

<80 ms to 5% of full scale

(1)

Calibrated accuracy, nom

Better than 0.1% of range @ 25 °C (77 °F)

Calibrated accuracy, max

0.025% of range @ 25 °C (77 °F)

Calibration interval

12 months

Offset drift

200

μ

A/°C

Gain drift with temperature, nom

17 ppm/°C
0.36

μ

A/°C

Gain drift with temperature, max

35 ppm/°C max
0.74

μ

A/°C max

Module error

0.2% of range

Module input scan time, min

25 ms min – floating point
10 ms min – integer

Isolation voltage

250V (continuous), basic insulation type, input
channels-to-backplane, and input channel-to-channel

Routine tested at 1350V AC for 2 s

Removable terminal block

1756-TBNH
1756-TBSH

Slot width

1

Wire size

0.33… 2.1 mm

2

(22…14 AWG) solid or stranded copper

wire rated at 90 °C (194 °F), or greater, 1.2 mm
(0.047 in.) insulation max

(2)

Wire category

2

(3)

North American temperature code

T4A

IEC temperature code

T4

Enclosure type

None (open-style)

(1)

Notch filter dependent.

(2)

Maximum wire size requires extended housing, catalog number 1756-TBE.

(3)

Use this conductor category information for planning conductor routing as described in the system-level

installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication

1770-4.1.

Technical Specifications - 1756-IF6CIS

Attribute

1756-IF6CIS

Advertising