1756-if16 channel status word bits – integer mode – Rockwell Automation 1756-XXXX ControlLogix Analog I/O Modules User Manual

Page 84

Advertising
background image

84

Publication 1756-UM0009C-EN-P - December 2010

Chapter 4 Non-isolated Analog Voltage/Current Input Modules (1756-IF16, 1756-IF8)

1756-IF16 Channel Status Word Bits – Integer Mode

The Channel Status word has these differences when the 1756-IF16 module is
used in integer mode.

• Only Underrange and Overrange conditions are reported by the

module.

• Alarming and Calibration Fault activities are not available, although the

Calibration Fault bit in the Module Fault word activates if a channel is
not properly calibrated.

• There is one, 32-bit Channel Status word for all 16 channels.

When the Calibration Fault bit (bit 7) is set in any of the words, the Calibration
Fault bit (bit 9) is set in the Module Fault word. The table lists the conditions
that set each of the words.

Tag (Status
word)

Bit

Event that sets this tag

ChxUnderrange

Odd-numbered bits from
31…1 ( bit 31 represents
channel 0).

For a full listing of the
channels these bits
represent, see

page 82

.

The underrange bit is set when the input signal at the channel is less than or
equal to the minimum detectable signal.

For more information on the minimum detectable signal for each module, see

page 61

. This bit also sets the appropriate bit in the Channel Fault word.

ChxOverrange

Even-numbered bits from
30 …0 (bit 30 represents
channel 0).

For a full listing of the
channels these bits
represent, see on

page 82

.

The overrange bit is set when the input signal at the channel is greater than
or equal to the maximum detectable signal.

For more information on the maximum detectable signal for each module, see

page 61

. This bit also sets the appropriate bit in the Channel Fault word.