Appendix A Analog I/O Module Specifications

Current draw @ 24V

210 mA

Power dissipation, max

4.92 W, 4 channel current

Thermal dissipation

16.78 BTU/hr

Open circuit detection

Current output only (Output must be set to >0.1 mA)

Overvoltage protection

24V DC

Short circuit protection

Electronically current limited to 21 mA or less

Drive capability

Voltage: > 2000

Ω

Current: 0…750

Ω

Settling time

< 2 ms to 95% of final value with resistive loads

Calibrated accuracy

4…21 mA, -10.4…10.4V: Better than 0.05% of range @
25 °C

Calibration interval

12 months

Offset drift

50

μ

V/°C

100 nA/°C1

μ

A/°C

Gain drift with temperature

Voltage: 25 ppm/°C max
Current: 50 ppm/°C max

Module error

Voltage: 0.15% of range
Current: 0.3% of range

Module scan time

12 ms min floating point
8 ms min integer

Isolation voltage

250V (continuous), reinforced insulation type, output
channels-to-backplane
No isolation between individual output channels

Routine tested at 1350V AC for 2 s

Removable terminal block

1756-TBNH
1756-TBSH

Slot width

1

Wire size

0.33…2.1 mm

2

(22…14 AWG) solid or stranded copper

wire rated at 90 °C (194 °F), or greater, 1.2 mm
(0.047 in.) insulation max

(1)

Wire category

2

(2)

North American temperature code

T4A

IEC temperature code

T4

Enclosure type

None (open-style)

(1)

Maximum wire size requires extended housing, catalog number 1756-TBE.

(2)

Use this conductor category information for planning conductor routing as described in the system-level

installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication

1770-4.1.

Technical Specifications - 1756-OF8

Attribute

1756-OF8