Fault reporting in floating point mode – Rockwell Automation 1756-XXXX ControlLogix Analog I/O Modules User Manual

Page 142

Advertising
background image

142

Publication 1756-UM009C-EN-P - December 2010

Chapter 6

Temperature-measuring Analog Modules (1756-IR6I, 1756-IT6I, and 1756-IT6I2)

Fault Reporting in Floating
Point Mode

The illustration offers an overview of the fault reporting process in floating
point mode.

Module Fault Word
(described on

page 143

)

Channel Fault Word
(described on

page 143

)

Channel Status Words
(one for each channel –
described on

page 144

)

15

14

13

12

11

10

9

8

5

4

3

2

1

0

5

4

3

2

1

0

7

6

15 = AnalogGroupFault
14 = InGroupFault
12 = Calibrating
11 = Cal Fault
9 = CJUnderrange (IT6I only)
8 = CJOverrange (IT6I only)
13 and 10 are not used by
1756-IR6I or 1756-IT6I

5 = Ch5Fault
4 = Ch4Fault
3 = Ch3Fault
2 = Ch2Fault
1 = Ch1Fault
0 = Ch0Fault

7 = ChxCalFault
6 = ChxUnderrange
5 = ChxOverrange
4 = ChxRateAlarm

41345

3 = ChxLAlarm
2 = ChxHAlarm
1 = ChxLLAlarm
0 = ChxHHAlarm

Cold Junction temperature underrange
and overrange conditions set bits 9 and 8
for 1756-IT6I only. You must monitor
these conditions here.

Any bit in the Channel Fault word, also sets the Analog
Group Fault and Input Group Fault in Module Fault word

A channel
calibration fault
sets the calibration
fault in the Module
Fault word

Alarm bits in the Channel Status word
do not set additional bits at any higher
level. You must monitor these
conditions here.

An underrange, overrange condition
sets appropriate Channel Fault bits

When the module is
calibrating, all bits in
the Channel Fault
word are set