Module resolution (-12…78 mv range) – Rockwell Automation 1756-XXXX ControlLogix Analog I/O Modules User Manual
Page 377

Publication 1756-UM009C-EN-P - December 2010
377
Additional Specification Information Appendix E
Module Resolution (-12…78 mV Range)
The table lists the resolution of ControlLogix thermocouple modules when
used in the -12…78 mV input range.
The information represented in the table is shown graphically in the
following illustrations.
0.00
0.02
0.04
0.06
0.08
0.10
0.12
0.14
0.16
0.18
0.20
-200
0
200
400
600
800
1000
1200
1400
1600
1800
Minimum Amount of
Degree Change Required
for Thermocouple Module
to Report the Change
Application Temperature in °C
Thermocouple Module Resolution - TypeT Thermocouple Connection in a -12…30 mV Input Range
Application
Temperature
Module Resolution (in degrees) When Connected to This Thermocouple Type
B
R
S
E
J
K
N
T
-200 °C (-328 °F)
0.056
0.064
0.046
0.141
0.089
0 °C (32 °F)
0.26
0.26
0.024
0.028
0.092
0.054
0.036
200 °C (392 °F)
0.16
0.17
0.019
0.025
0.035
0.042
0.026
400 °C (752 °F)
0.28
0.14
0.15
0.017
0.025
0.035
0.038
0.023
600 °C (1112 °F)
0.23
0.12
0.14
0.017
0.024
0.033
0.04
800 °C (1472 °F)
0.18
0.11
0.13
0.018
0.022
0.033
0.04
1000 °C (1832 °F)
0.15
0.11
0.12
0.019
0.024
0.034
0.04
1200 °C (2192 °F)
0.14
0.10
0.12
0.024
0.036
0.04
1400 °C (2552 °F)
0.12
0.10
0.12
0.038
1600 °C (2912 °F)
0.12
0.10
0.12
1800 °C (3272 °F)
0.12
0.11
0.14