Rockwell Automation 1756-XXXX ControlLogix Analog I/O Modules User Manual

Page 300

Advertising
background image

300

Publication 1756-UM009C-EN-P - December 2010

Appendix A Analog I/O Module Specifications

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

1756-IR6I 4-wire RTD

4-wire RTD

Shield Ground

IN-1/A

IN-1/B

RTN-1/C

IN-3/A

IN-3/B

RTN-3/C

Not used

IN-5/A

IN-5/B

RTN-5/C

IN-0/A

IN-0/B

RTN-0/C

IN-2/A

IN-2/B

RTN-2/C

Not used

IN-4/A

IN-4/B

RTN-4/C

· Do not connect more than two wires to any single terminal.
· Wiring is exactly the same as the three--wire RTD with one wire left open.

Input Signal to User Count Conversion - 1756-IR6I

Range

Low Signal and User Counts

High Signal and User Counts

1...487

Ω

0.859068653

Ω

-32768 counts

507.862

Ω

32767 counts

2...1000

Ω

2

Ω

-32768 counts

1016.502

Ω

32767 counts

4...2000

Ω

4

Ω

-32768 counts

2033.780

Ω

32767 counts

8...4020

Ω

8

Ω

-32768 counts

4068.392

Ω

32767 counts

Technical Specifications - 1756-IR6I

Attribute

1756-IR6I

Inputs

6 individually isolated RTD

Input range

1…487

Ω

2…1000

Ω

4…2000

Ω

8…4020

Ω

Resolution

16 bits
1…487

Ω

: 7.7 m

Ω

/bit

2…1000

Ω

: 15 m

Ω

/bit

4…2000

Ω

: 30 m

Ω

/bit

8…4020

Ω

: 60 m

Ω

/bit

ANALOG INPUT

CAL

OK