Module Fault Word Bits – Integer Mode

In integer mode, Module Fault word bits (bits 15…11) operate exactly as
described in floating point mode. The table lists tags that are found in the
Module Fault Word.

Channel Fault Word Bits – Integer Mode

In integer mode, Channel Fault word bits (bits 5…0) operate exactly as
described in floating point mode for calibration and communications faults.
The table lists the conditions that set

all Channel Fault word bits.

Your logic should monitor the Channel Fault bit for a particular output, if you
either:

• set the high and low limit alarms outside your operating range

• disable output limiting.

Tag

Description

Analog Group
Fault

This bit is set when any bits in the Channel Fault word are set. Its tag
name is AnalogGroupFault.

Output Group
Fault

This bit is set when any bits in the Channel Fault word are set. Its tag
name is OutputGroupFault.

Calibrating

This bit is set when any channel is being calibrated. When this bit is
set, all bits in the Channel Fault word are set. Its tag name is
Calibrating.

Calibration Fault

This bit is set when any of the individual Channel Calibration Fault bits
are set. Its tag name is CalibrationFault.

This condition sets all Channel
Fault word bits

And causes the module to display the
following in the Channel Fault word bits

A channel is being calibrated

’003F’ for all bits

A communications fault occurred
between the module and its
owner-controller

’FFFF’ for all bits