Wire the 1756-IF16 Module

Current and voltage wiring examples for the 1756-IF16 module are shown on
the following pages.

1756-IF16 Differential Current Wiring Example.

+

-

+

-

40912-M

1
3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33
35

36

IN-0

IN-10

IN-1

IN-9

IN-2

IN-8

IN-5

IN-3

IN-6

RTN

IN-7

IN-4

IN-13

IN-12

IN-14

IN-11

RTN

i RTN-0

i RTN-7

i RTN-4

i RTN-6

i RTN-8

i RTN-9

i RTN-10
i RTN-11
RTN
i RTN-12
i RTN-13

RTN

i RTN-5

i RTN-1
i RTN-2
i RTN-3

IN-15

i RTN-14
i RTN-15

Shield Ground

Channel 0

Channel 3

Jumper Wires

i

i

A

NOTES:

1. Use the table when wiring your module in differential mode

2. All terminals marked RTN are connected internally.

3. A 249

Ω

current loop resistor is located between IN-x and i RTN-x terminals.

4. If multiple (+) or multiple (-) terminals are tied together, connect that tie point to a RTN terminal to

maintain the module’s accuracy.

5. Place additional loop devices (strip chart recorders, so forth) at the A location in the current loop.

6. Do not connect more than two wires to any single terminal.

IMPORTANT: When operating in four channel, high-speed mode, only use channels 0, 2, 4 and 6.

Channel

Terminals

Channel

Terminals

Channel 0

IN-0 (+), IN-1 (-) & i RTN-0

Channel 4

IN-8 (+), IN-9 (-) & i RTN-8

Channel 1

IN-2 (+), IN-3 (-) & i RTN-2

Channel 5

IN-10 (+), IN-11 (-) & i RTN-10

Channel 2

IN-4 (+), IN-5 (-) & i RTN-4

Channel 6

IN-12 (+), IN-13 (-) & i RTN-12

Channel 3

IN-6 (+), IN-7 (-) & i RTN-6

Channel 7

IN-14 (+), IN-15 (-) & i RTN-14

2-Wire
Transmitter

A

+

4-Wire
Transmitter

Shield Ground

Channel 6

i

A

2

34

User-provided
Loop Power

Device
Supply