Calibrate the ControlLogix Analog I/O Modules Chapter 11

5.

Click the Calibration Tab on the Module Properties dialog box.

6.

Click Start Calibration to access the Calibration Wizard to step through
the process.

If your module is not in Program mode, a warning message appears.
You must manually change the module to Program mode before
clicking Yes.

7.

Set the channels to be calibrated.