Analog I/O Module Specifications Appendix A

Thermocouples

B, E, J, K, R, S, T, N, C

Current draw @ 5.1V

250 mA

Current draw @ 24V

125 mA

Power dissipation, max

4.3 W

Thermal dissipation

14.66 BTU/hr

Input impedance

>10 M

Ω

Open circuit detection time

Positive full scale reading within 2 s

Overvoltage protection, max

120V AC/DC

Normal mode noise rejection

60 dB at 60 Hz

(1)

Common mode noise rejection

120 dB @ 60 Hz
100 dB @ 50 Hz

Channel bandwidth

15 Hz (-3 dB)

(1)

Settling time

<80 ms to 5% of full scale

(1)

Calibrated accuracy @ 25 °C

Better than 0.1% of range

Calibration interval

6 months

Local CJC sensor accuracy

±0.3…3.2 °C, depending on channel

Remote CJC sensor accuracy

±0.3 °C

Offset drift

0.5

μ

V/°C

Gain drift with temperature

65 ppm/°C, 80 ppm/°C max

Module error

0.5% of range

Module scan time

25 ms min floating point (millivolt)
50 ms min floating point (temperature)
10 ms min integer (millivolt)

(1)

Isolation voltage

250V (continuous), basic insulation type, input channels
to backplane, and input channel to channel

Routine tested at 1350V AC for 2 s

Removable terminal block

1756-TBNH
1756-TBSH

Slot width

1

Wire size

0.33… 2.1 mm

2

(22…14 AWG) solid or stranded copper

wire rated at 90 °C (194 °F), or greater, 1.2 mm
(0.047 in.) insulation max

(2)

Wire category

2

(3)

North American temperature code

T4A

IEC temperature code

T4

Enclosure type

None (open-style)

(1)

Notch filter dependent.

(2)

Maximum wire size requires extended housing, catalog number 1756-TBE.

(3)

Use this conductor category information for planning conductor routing as described in the system-level

installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication

1770-4.1.

Technical Specifications - 1756-IT6I

Attribute

1756-IT6I

Advertising