130

Publication 1756-UM009C-EN-P - December 2010

Chapter 6

Temperature-measuring Analog Modules (1756-IR6I, 1756-IT6I, and 1756-IT6I2)

To see how to choose a thermocouple sensor type, see

page 216

.

Temperature Units

The 1756-IR6I, 1756-IT6I and 1756-IT6I2 modules provide the choice of
working in Celsius or Fahrenheit. This choice affects all channels per module.

To see how to choose temperature units, see

page 215

.

Input Signal to User Count Conversion

Integer mode does not support temperature conversion on
temperature-measuring modules. However, this mode can be used by the
1756-IT6I and 1756-IT6I2 modules to calculate user counts for both available
millivolt ranges.

The straight line formulas that can be used to calculate or program a Compute
(CPT) instruction are shown in the table.

For example, if you have 24 mV in the -12…30 mV range, the
user counts = 22498. Counts = -20856 for 2 mV in the 12…78 mV range.

For a table with related values, refer to ControlLogix 1756-IT6I
and 1756-IT6I2 mV Input Signal to User Count Conversion, Knowledgebase
Technical Note ID 41567.

IMPORTANT

The table lists temperature limits for sensors using the
-12…78 mV range only. When the -12…30 mV range is used,
temperature limits are truncated to the temperature value that
corresponds to 30 mV.

Available Range

User Count Formula

-12…30 mV

y = 1388.4760408167676x-10825.593777483234

where y = counts; x = mV

12…78 mV

y = 694.2314015688241x-22244.5904917152

where y = counts; x = mV