Troubleshoot your module, Introduction, Chapter 12 – Rockwell Automation 1756-XXXX ControlLogix Analog I/O Modules User Manual

Page 273: Status indicators for input modules, Chapter

Advertising
background image

Publication 1756-UM009C-EN-P - December 2010

273

Chapter

12

Troubleshoot Your Module

Introduction

Each ControlLogix analog I/O module has status indicators that display
module status. This chapter describes the status indicators, located on the
front of a module, and how to use these visual signals to troubleshoot
anomalies.

Status indicators show the I/O module state (green), or fault (red).

Status Indicators for Input Modules

The illustration and table show the status indicators used with analog
input modules.

Topic

Page

Status Indicators for Input Modules

273

Status Indicators for Output Modules

274

Use RSLogix 5000 Software for Troubleshooting

275

Status Indicator

Display

Description

Action

OK

Steady green light

The inputs are being multicast and in
normal operating state.

None

OK

Flashing green light

The module has passed internal
diagnostics but is not currently
performing connected communication.

None

OK

Flashing red light

Previously established communication
has timed out.

Check controller and
chassis communication

OK

Steady red light

The module must be replaced.

Replace the module.

CAL

Flashing green light

The module is in Calibration mode.

Finish calibration

20962-M

ANALOG INPUT

CAL

OK