Analog I/O Tag Definitions Appendix B

Integer Configuration Tags

Integer Configuration Tags

Tag Name

Data Type

Applicable
Modules

Definition

CJDisable

BOOL

All inputs (only
used for the
1756-IT6I and
1756-IT6I2)

Disables the cold junction sensor that turns off cold junction compensation
when linearizing thermocouple inputs.

RealTimeSample

INT

All input

Determines how often the input signal is to be sampled in terms of
milliseconds.

Ch0RangeNotch

SINT

1756-IF6CIS,
1756-IF6I,
1756-IR6I,
1756-IT6I and
1756-IT6I2

Configures the channel’s input range and notch filter settings. The input range
is the upper nibble (bits 4…7) and determines the signal range the input
channel can detect. Input range values are as listed.

0 = -10…10V (1756-IF6I)
1 = 0…5V (1756-IF6I)
2 = 0…10V (1756-IF6I)
3 = 0…20 mA (1756-IF6CIS and 1756-IF6I)
4 = -12…78 mV (1756-IT6I and 1756-IT6I2)
5 = -12…30 mV (1756-IT6I and 1756-IT6I2)
6 = 1…487

Ω

(1756-IR6I)

7 = 2…1,000

Ω

(1756-IR6I)

8 = 4…2,000

Ω

(1756-IR6I)

9 = 8…4,020

Ω

(1756-IR6I)

The notch filter provides superior frequency filtering at the selected value and
its harmonics. The notch filter is the lowest nibble (bits 0…3).

0 = 10 Hz
1 = 50 Hz
2 = 60 Hz
3 = 100 Hz
4 = 250 Hz
5 = 1,000 Hz

ProgToFaultEn

BOOL

All outputs

The program to fault enable bit determines how the outputs should behave if a
communication fault were to occur while the output module is in the Program
mode. When set, the bit causes the outputs to transition to their programmed
Fault state if a communication fault occurs while in the Program state. If not
set, outputs will remain in their configured program state despite a
communication fault occurring.

Ch0Config

SINT

All outputs

Contains all individual configuration bits for channel.