Configure ControlLogix Analog I/O Modules Chapter 10
Connection Tab
The Connection tab on the Module Properties dialog box lets you enter a
requested packet interval (RPI), inhibit a module, and set a connection fault
when the module is in Run mode. The RPI provides a defined, maximum
period of time when data is transferred to the owner-controller.
1.
Choose from the options on the Connection tab.
Field Name
Description
Requested Packet Interval (RPI)
Enter an RPI value or use the default.
Requested Packet Interval (RPI)
in
Chapter 2 for more information.
Inhibit Module
Check the box to prevent
communication between the
owner-controller and the module. This
option allows for maintenance of the
module without faults being reported to
the controller.
in Chapter 3 for
more information.
Major Fault On Controller If Connection
Fails While in Run Mode
Check the box to create a major fault if
there is a connection failure with the
module while in Run mode.
For important information on this
checkbox, see ‘Configure a Major Fault
to Occur’ in the Logix5000 Controllers
Information and Status Programming
Manual, publication