ControlLogix Analog I/O Module Features Chapter 3

The table lists the conversions a generated digital signal to the number
of counts.

Floating point mode

This mode lets you change the data representation of the selected module.
Although the full range of the module does not change, you can scale your
module to represent I/O data in terms specific for your application.

For example, if you are using the 1756-IF6I module in floating point mode and
choose an input range of 0 mA…20 mA, the module can use signals within the
range of 0 mA…21 mA but you can scale the module to represent data
between 4 mA…20mA as the low and high signals in engineering units as
shown on

page 50

.

For an example of how to define data representation in engineering units
through RSLogix 5000 software, see

page 210

.

Output Signal to User Count Conversion

Output Module

Available
Range

Low Signal and
User Counts

High Signal and
User Counts

1756-OF4/OF8

0…20 mA

0 mA

-32768 counts

21.2916 mA

32767 counts

+/- 10V

-10.4336V

-32768 counts

10.4336V

32767 counts

1756-OF6CI

0…20 mA

0 mA

-32768 counts

21.074 mA

32767 counts

1756-OF6VI

+/- 10V

-10.517V

-32768 counts

10.517V

32767 counts