Application notes for FactoryTalk Transaction Manager Appendix D

GO

SET QUOTED_IDENTIFIER OFF

GO

SET ANSI_NULLS ON

GO

In FactoryTalk Transaction Manager, configure:

• A scheduled or device-scheduled data point defined as a signed

short, pointing to the result tag.

• A scheduled or device-scheduled data point defined as PLC

TimeStamp, pointing to Current[0],L6 with the size of 6
elements.

• A scheduled or device-scheduled data point defined as signed

long, pointing to New[0],L6 with the size of 6 elements.

• A data object pointing to the stored procedure in the database.

Perform the steps described below for RSLogix 5000 and
FactoryTalk Transaction Manager to send date/time information
from a ControlLogix processor to a database:

• In RSLogix 5000 (page 281).
• In FactoryTalk Transaction Manager (page 282).

Perform the following steps:

1. Create a controller tag of the following type:

SystemTimeDINT, style=decimal, Type =DINT[7]

2. Create a controller tag of the following type:

SystemTimeINT, style=decimal, Type=INT[7]

3. In the ladder logic, add a rung with the instruction GSV.

Get system value

CIP Object class:

WALLCLOCKTIME

CIP Object name:

-

In FactoryTalk Transaction
Manager

Getting date/time
information from a
ControlLogix processor to a
database

In RSLogix 5000

Rockwell Automation Publication BZWARE-IN001M-EN-P-June 2014

281