Table 38, Table 39, Table 40 – Rockwell Automation 7763 Medium Voltage OneGear SMC Flex Motor Controller (10-15 kV) User Manual

Page 101

Advertising
background image

Rockwell Automation Publication 7760-UM001D-EN-P - October 2014

101

Troubleshooting

Chapter 8

Table 38 - Motor Stops While Running

Table 39 - Irregular Starts

Note:

Although the default settings accommodate the vast majority of

applications, these tuning parameters may require more than one adjustment to
achieve optimal results. Some parameters are affected by motor loading and
power system conditions, so one setting may not be optimal for all conditions.

Table 40 - Miscellaneous Situations

(1)

Display

Possible Causes

Possible Solutions

Fault displayed

See fault description

See

Table 35

addressing fault conditions

Display is blank

Control voltage is absent
Failed control module

Check control wiring and correct if necessary
Replace control module

Stopped 0.0 A

Pilot devices
Failed control module

Check control wiring and correct if necessary
Replace control module

Starting

Two or three power phases are missing
Failed control module

Check power system
Check voltage sensing module and connections
Replace control module

Symptom

Possible Causes

Possible Solutions

Bypass contactor closes before motor is up to speed

Ramp time too short
Motor characteristics cause Up-to-Speed sensing too

early

Increase ramp time (parameter 18)
Adjust parameter 114 higher (no more than 5% at a

time)

Motor is up to speed but bypass contactor is delayed in
closing or does not close at all

Ramp time too long
Motor characteristics cause Up-to-Speed sensing too

late or not at all

Decrease ramp time
Adjust parameter 114 lower (no more than 5% at a

time)

Rough start, erratic current, growling from the motor
(may see Line Faults)

Poor grounding of the power system or controller
Poor power quality, electrical noise, harmonics, VFD

line notching

Resolve ground issues
Adjust parameter 117 higher. Typical settings are 35 or

40. Not recommended to exceed 75 or go below 25.

During a Pump Stop, the motor takes more than 5 seconds
to begin to decelerate or takes longer than the
programmed stop time

Motor or pump characteristics do not match the

default setting

Adjust parameter 34 to between 20 and 30 (not

recommended to go above 40).

(1) Various faults may occur if Parameter #15 is set to "Delta". It must be set to "Line" for all MV applications.

Display

Possible Causes

Possible Solutions

Motor current and voltage fluctuates with steady load

Motor
Erratic Load

Verity type of motor as a standard squirrel cage

induction motor

Check load conditions

Erratic operation

Loose connections

Shut off all power to controller and check for loose

connections

Accelerates too fast

Starting time
Initial torque
Current limit setting
Kickstart

Increase starting time
Lower initial torque setting
Decrease current limit setting
Lower kickstart time or turn off

Accelerates too slow

Starting time
Initial torque
Current limit setting
Kickstart

Decrease starting time
Increase initial torque setting
Increase current limit setting
Increase kickstart time or turn off

Fan does not operate

Wiring
Failed fans(s)

Check wiring and correct if necessary
Replace fan(s)

Motor stops too quickly with Soft Stop option

Time setting

Verify the programmed stopping time and correct if

necessary