B - smc flex module parameter information, Table of parameters, Appendix b – Rockwell Automation 7763 Medium Voltage OneGear SMC Flex Motor Controller (10-15 kV) User Manual

Page 131: Smc flex module parameter information, Appendix

Advertising
background image

Rockwell Automation Publication 7760-UM001D-EN-P - October 2014

131

Appendix

B

SMC Flex Module Parameter Information

Table of Parameters

Table 50 - Parameter List

Group

Parameter
Name

Parameter
Number

Units

Min./ Max.

Default Settings

Parameter Description

User Settings

Metering Volts

Phase

A-B 1

V

Provides the phase-to-phase supply voltage
measurements at all times, including bypass
operation.

Metering Volts

Phase

B-C 2

V

Provides the phase-to-phase supply voltage
measurements at all times, including bypass
operation.

Metering Volts

Phase

C-A 3

V

Provides the phase-to-phase supply voltage
measurements at all times, including bypass
operation.

Metering

Current Phase A

4

A

Provides the phase A motor current measurement.

Metering

Current Phase B

5

A

Provides the phase B motor current measurement.

Metering

Current Phase C

6

A

Provides the phase C motor current measurement.

Metering Watt

Meter

7

KW/MW

Provides the power usage of the connected motor.
This value is calculated from the voltage, current
and power factor measurements.

Metering Kilowatt

Hours 8

KWH/
MWH

Provides the power usage over time of the
connected motor.

Metering Elapsed

Time 9

Hours

Indicates the total time of motor operation in hours.
The accumulated ime is updated continuously
during run time.

Metering

Meter Reset

10

NO ETM Reset
KWH Reset

NO

Provides the user the capability to reset the value
stored in the elapsed time (9) and kilowatt hours (8)
meters to zero.

Metering Power

Factor 11

0.00…0.99

Provides the operational displacement power factor
measurement of the connected motor.

Metering Mtr

Therm

Usage

12

%MTU 0…100

Provides the theoretical model of motor heating as
a percentage value. At 100% MTU, the controller
will fault on overload. This model is based on the
motor thermal overload calculation.

Metering Motor

Speed 13

%

0…100

Indicates the operating percentage of motor base
speed when linear ramp is selected and an external
tachometer is used.

Basic Set Up

SMC Option

14

Standard Brake
Pump Control

This a “read-only” parameter that identifies to the
user the type of control module installed.

Basic Set Up

Motor Connection

15

Line/Delta

Line

This parameter allows the user the ability to select
the power wiring configuration of the SMC to the
attached motor (WYE or DELTA). A fault controlled
means of disconnecting the line should always be
use in the DELTA mode.

Do not set to
“Delta”