B - smc flex module parameter information, Table of parameters, Appendix b – Rockwell Automation 7763 Medium Voltage OneGear SMC Flex Motor Controller (10-15 kV) User Manual
Page 131: Smc flex module parameter information, Appendix
Rockwell Automation Publication 7760-UM001D-EN-P - October 2014
131
Appendix
B
SMC Flex Module Parameter Information
Table of Parameters
Table 50 - Parameter List
Group
Parameter
Name
Parameter
Number
Units
Min./ Max.
Default Settings
Parameter Description
User Settings
Metering Volts
Phase
A-B 1
V
Provides the phase-to-phase supply voltage
measurements at all times, including bypass
operation.
Metering Volts
Phase
B-C 2
V
Provides the phase-to-phase supply voltage
measurements at all times, including bypass
operation.
Metering Volts
Phase
C-A 3
V
Provides the phase-to-phase supply voltage
measurements at all times, including bypass
operation.
Metering
Current Phase A
4
A
Provides the phase A motor current measurement.
Metering
Current Phase B
5
A
Provides the phase B motor current measurement.
Metering
Current Phase C
6
A
Provides the phase C motor current measurement.
Metering Watt
Meter
7
KW/MW
Provides the power usage of the connected motor.
This value is calculated from the voltage, current
and power factor measurements.
Metering Kilowatt
Hours 8
KWH/
MWH
Provides the power usage over time of the
connected motor.
Metering Elapsed
Time 9
Hours
Indicates the total time of motor operation in hours.
The accumulated ime is updated continuously
during run time.
Metering
Meter Reset
10
NO ETM Reset
KWH Reset
NO
Provides the user the capability to reset the value
stored in the elapsed time (9) and kilowatt hours (8)
meters to zero.
Metering Power
Factor 11
0.00…0.99
Provides the operational displacement power factor
measurement of the connected motor.
Metering Mtr
Therm
Usage
12
%MTU 0…100
Provides the theoretical model of motor heating as
a percentage value. At 100% MTU, the controller
will fault on overload. This model is based on the
motor thermal overload calculation.
Metering Motor
Speed 13
%
0…100
Indicates the operating percentage of motor base
speed when linear ramp is selected and an external
tachometer is used.
Basic Set Up
SMC Option
14
Standard Brake
Pump Control
This a “read-only” parameter that identifies to the
user the type of control module installed.
Basic Set Up
Motor Connection
15
Line/Delta
Line
This parameter allows the user the ability to select
the power wiring configuration of the SMC to the
attached motor (WYE or DELTA). A fault controlled
means of disconnecting the line should always be
use in the DELTA mode.
Do not set to
“Delta”