Ptc trip, Open gate, Ptc trip open gate – Rockwell Automation 7763 Medium Voltage OneGear SMC Flex Motor Controller (10-15 kV) User Manual

Page 34

Advertising
background image

34

Rockwell Automation Publication 7760-UM001D-EN-P - October 2014

Chapter 1

Product Overview

The following figure illustrates the required PTC sensor characteristics, per
IEC-34-11-2.

Figure 18 - PTC Sensor Characteristics per IEC-34-11-2

PTC Trip

The MV SMC Flex will trip with a PTC indication if:

No other fault currently exists

PTC protection is enabled

The resistance across terminals 23 and 24 is either greater than the relay’s
response resistance or less than the short-circuit trip resistance.

Open Gate

An open-gate fault indicates that improper SCR firing, typically caused by an
open SCR gate or driver system, has been detected on one of the power poles.
Before the controller shuts down, it will attempt to start the motor a total of three
times (or as programmed in Parameter 82).

An open gate is detected when the module sends a gate signal to the SCRs but
does not detect that they turned on. SCR turn-on is detected when the voltage
across the leg (L-T) collapses. The Open Gate detection is active during starting
or stopping only.