Human interface module, Keypad description – Rockwell Automation 7763 Medium Voltage OneGear SMC Flex Motor Controller (10-15 kV) User Manual

Page 86

Advertising
background image

86

Rockwell Automation Publication 7760-UM001D-EN-P - October 2014

Chapter 7

Communications

Human Interface Module

The SMC Flex controller can be programmed with the built-in keypad and LCD
display or with the optional Bulletin 20HIM LCD human interface modules.
Parameters are organized in a three-level menu structure and divided into
programming groups.

Note:

Node addressing of the DPI communication card can be programmed via

software or a hand-held DPI HIM. The onboard HIM cannot be used to address
the communication card.

Keypad Description

The functions of each programming key are described below.

Table 26 - Keypad Descriptions

Note:

If a human interface module is disconnected from the SMC Flex controller

while the Logic Mask is set to 1, a “Coms Loss” will occur.

Note:

For ease of programming values, after using the Enter key to edit, use the

Sel key to jump to the digit that needs to be modified, then use the arrow keys to
scroll through the digits.

The Bulletin 20-HIM LCD interface modules may be used to program and
control the SMC Flex controller. The human interface modules have two
sections: a display panel and a control panel. The display panel duplicates the 3-
line, 16-character backlit LCD display and programming keypad found on front
of the SMC Flex controller. Refer to Chapter 4 for a description of the
programming keys; refer to Appendix D for a listing of human interface module
catalog numbers that are compatible with the controller.

Note:

Bulletin 20-HIM Rev3.002 or later must be utilized with the SMC Flex.

Note:

Extension cables are available up to a maximum of 10 m in total length.

Note:

A maximum of two HIM modules can be installed.

The control panel provides the operator interface to the controller.

Key

Name

Description

Escape

Exit a menu, cancel a change to a parameter value, or acknowledge a fault/alarm.

Select

Select a digit, select a bit, or enter edit mode in a parameter screen.

Up/Down Arrows

Scroll through options increase/decrease a value, or toggle a bit.

Enter

Enter a menu, enter edit mode in a parameter screen, or save a change to a parameter value.

Esc

Esc

Sel

Sel

Advertising