Rockwell Automation Publication 7760-UM001D-EN-P - October 2014

89

Communications

Chapter 7

Figure 39 - Port Number Displayed

3.

Go to Logic Mask, found as follows:

Main Menu: Parameter/Communications/Comm Mask/Logic Mask

Figure 40 - Logic Mask Displayed

4.

Set b0X equal to 1 (where X is the port number noted in

step 2

).

5.

Go to Parameter Management and save as User Store.

If enabling control from the built-in SMC Flex programmer, the Logic Mask
must be set as follows:

Table 29 - Logic Mask Requirements

IMPORTANT

The Logic Mask must be set to 0 prior to disconnecting a human interface
module from the SMC Flex controller. If not, the unit will fault on a “Coms Loss”.

Mask Code

Description

0

No external DPI devices are enabled

4

Only one HIM on port 2 is enabled

12

Two HIMs are enabled on ports 2 and 3