Rockwell Automation 7763 Medium Voltage OneGear SMC Flex Motor Controller (10-15 kV) User Manual
Page 89
Rockwell Automation Publication 7760-UM001D-EN-P - October 2014
89
Communications
Chapter 7
Figure 39 - Port Number Displayed
3.
Go to Logic Mask, found as follows:
Main Menu: Parameter/Communications/Comm Mask/Logic Mask
Figure 40 - Logic Mask Displayed
4.
Set b0X equal to 1 (where X is the port number noted in
).
5.
Go to Parameter Management and save as User Store.
If enabling control from the built-in SMC Flex programmer, the Logic Mask
must be set as follows:
Table 29 - Logic Mask Requirements
IMPORTANT
The Logic Mask must be set to 0 prior to disconnecting a human interface
module from the SMC Flex controller. If not, the unit will fault on a “Coms Loss”.
Mask Code
Description
0
No external DPI devices are enabled
4
Only one HIM on port 2 is enabled
12
Two HIMs are enabled on ports 2 and 3