Rockwell Automation 7763 Medium Voltage OneGear SMC Flex Motor Controller (10-15 kV) User Manual
Page 122
122
Rockwell Automation Publication 7760-UM001D-EN-P - October 2014
Appendix A
7760, 7761, 7762, and 7763 SMC Flex Specifications
Approvals
Safety: 92/59/EEC (Directive)
Ref:BSEN 61010-1:1993
BSEN 60204-1:1997
IEC 62271-1
IEC 62271-200
IEC 60146-1-1
IEC 60947-4-2
Short Circuit Protection
The power electronics unit must be protected by current-limiting fuses or a fast-acting circuit breaker. The standard 12 kV combination controller includes appropriate fusing
(coordinated with motor).
Fault Level Withstand
(1)
31.5 kA 100 ms
Control Circuit
Rated Operation Voltage
120/240V AC (-15%, +10%) / 115/230V ~ (-15%, +10%)
Dielectric Withstand
1600V AC / 2000V ~
Operating Frequency
50/60 Hz
Enclosure
Enclosure Type
IP4X, IP41 and IP42
Overload Characteristics (SMC Flex Control Module)
Type
Solid-state thermal overload with phase loss
Current Range
1.0…1,000 A
Trip Classes
10, 15, 20 and 30
Trip Current Rating
117% of Motor FLC
Number of Poles
3
Power Requirements
Control Module
Self-powered, 75VA
Gate Driver Boards
(2)
75VA (total)
Vacuum Contactor/Breaker
Refer to Contactor/Breaker Specifications
Auxiliary Contacts (Control Module)
Rated Operation Voltage (Max.)
20…265V ~5…30V DC (resistive)
Rated Insulation Voltage
277V ~
Operating Frequency
50/60 Hz, DC
Conventional thermal current Ith
5 A
Utilization Category
AC-15/DC-12
Mechanical Ratings (Control Module)
Terminals
Control Terminals:
M 3.5 x 0.6 Pozidriv screw with self-lifting clamp plate
SCPD Performance
Type 2
SCPD List
Class CC 8A @ 1000 A Available Fault Current
DPI Communication (Control Module)
Maximum Output Current
280 mA
Metering Functionality (Control Module)
Voltage, Current, MW, MWh, Displacement Power Factor
Yes
Electrical Ratings
IEC