Appendix B

SMC Flex Module Parameter Information

Unbalance

Unbalance A Dly

66

Secs

0…99

0

Allows the user the ability to prevent some nuisance
Alarms by entering a delay period that provides a
window that the voltage unbalance condition must
persist within for the controller to Alarm.

Jam

Jam F Lvl

67

%FLC

0…1000

0

Allows the user to set an instantaneous over current
level (% of line FLC) that will cause a fault. A zero
value is the “off” setting.

Jam

Jam F Dly

68

Secs

0…99

0

Allows the user the ability to prevent some nuisance
faults by entering a delay period that provides a
window that the motor over current condition must
persist within for the controller to fault.

Jam Jam

A

Lvl 69 %FLC

0…1000

0

Allows the user to set an instantaneous over current
level (% of line FLC) that will cause an Alarm. A zero
value is the “off” setting.

Jam Jam

A

Dly 70 Secs

0…99 0

Allows the user the ability to prevent some nuisance
Alarms by entering a delay period that provides a
window that the motor over current condition must
persist within for the controller to Alarm.

Stall Stall

Delay 71 Secs

0.0…10.0

0

This feature allows the user to program the amount
of time beyond the initial start maneuver for the
motor to be at speed. A setting of zero means that
the stall detection feature is disabled.

1 sec
recommended

Ground Fault Gnd Flt Enable

72

Disable
Enable

Disable

Enables ground fault protection when used with an
external core balanced ground fault sensor.

Ground Fault Gnd Flt Level

73

A

1.0…5.0

2.5

Allows the user to set a current (core balance
current) that will cause a fault when the current is
above this value.

Ground Fault Gnd Flt Delay

74

Secs

0.1…250.0

0.5

Allows the user the ability to prevent some nuisance
faults by entering a delay period that provides a
window that the ground fault condition must
persist within for the controller to fault.

Ground Fault Gnd Flt Inh Time

75

Secs

0…250

10

Allow the user the ability to disable/inhibit ground
fault protection for a selected time when starting.

Ground Fault Gnd Flt A Enable

76

Disable
Enable

Disable

Enables a ground fault protection Alarm when used
with an external core balanced ground fault sensor.

Ground Fault Gnd Flt A Lvl

77

A

1.0…5.0

2.0

Allows the user to set a current (core balance
current) that will cause an Alarm when the current
is above this value.

Ground Fault Gnd Flt A Dly

78

Secs

0…250

10

Allows the user the ability to prevent some nuisance
Alarms by entering a delay period that provides a
window that the ground fault condition must
persist within for the controller to Alarm.

PTC PTC

Enable

79

Disable
Enable

Disable

Enables PTC based over-temperature protection
when used with external PTC sensors.

Phase
Reversal

Phase Reversal

80

Disable
Enable

Disable

Allows the user to prevent starting if the incoming
line phase sequence is not correct. The incoming
power lines are expected to be in an ABC sequence.
The controller will fault if power lines are out of the
ABC sequence.

Restart

Starts Per Hour

81

0…99

0

Limits the number of starts that can occur in a one-
hour period. This feature includes a “sliding
window” for the one-hour time period.

2 recomMended

Restart Restart

Attempts

82

0…5

0

Allows the user to enable the SMC-Flex to auto-
restart for up-to 5 attempts, other than an SCR
overtemp or motor overload fault. The start signal
must remain active for a restart to occur.

Group

Parameter
Name

Parameter
Number

Units

Min./ Max.

Default Settings

Parameter Description

User Settings