Control module removal – Rockwell Automation 7763 Medium Voltage OneGear SMC Flex Motor Controller (10-15 kV) User Manual

Page 102

Advertising
background image

102

Rockwell Automation Publication 7760-UM001D-EN-P - October 2014

Chapter 8

Troubleshooting

Note:

For Pump Stop issues, please refer to

Pump Application Considerations on

page 39

.

Control Module Removal

The control module is not intended for field repair. The entire module must be
replaced in the event of failure. The following procedure must be followed before
unplugging the control module.

1.

Remove all power from the equipment.

2.

Make sure that the wires are properly marked and that the program
parameters are recorded.

3.

Disconnect all control wires to control module.

4.

Loosen the four control module screws.

5.

Carefully rotate the module to the left, and unplug the five ribbon cables
from the interface board.

Motor stops too slowly with Soft Stop option

Stopping time setting
Misapplication

Verify the programmed stopping time and correct if

necessary

The Soft Stop option is intended to extend the

stopping time for loads that stop suddenly when
power is removed from the motor.

Fluid surges with pumps still occur with the Soft Stop
option

Misapplication

Soft Stop ramps voltage down over a set period of

time. In the case of pumps, the voltage may drop too
rapidly to prevent surges. A closed loop system such as
Pump Control would be more appropriately suited.

Motor overheats

Overload
Blocked ventilation
Duty cycle

Allow motor to cool and reduce load.
Remove blockage and ensure motor is being

adequately cooled.

Preset Slow Speed and Accu-Stop options: Extended

operation at slow speeds reduces motor cooling
efficiency. Consult motor manufacturer for motor
limitations.

Smart Motor Braking option: Check duty cycle. Consult

motor manufacturer for motor limitations.

Motor short circuit

Winding fault

Identify fault and correct
Check for shorted SCR; replace if necessary
Ensure power terminals are secure

Motor coasts when option stop is programmed

Option not programmed
Current loop power supply not active
Incorrect control logic

Verify the option parameter settings and correct if

necessary

Verify current loop power supply (see

Resistance

Checks and Power Supply Tests

)

Verify connections to module terminals 16 and 17 (see

Functional Description on page 44

)

Display

Possible Causes

Possible Solutions

SHOCK HAZARD: To avoid shock hazard, ensure the main power has been
disconnected before working on the controller, motor or control devices. Verify
that all circuits are voltage free using a hot stick or appropriate voltage
measuring device. Failure to do so may result in burns, injury or death.

Advertising