Chapter 2

Commissioning Procedure

Figure 27 - Connection and Test Information for Interface Board

L N G

TB5

TB21

I-A

I-B

I-C

VCOM

LINE A

LOAD A

LINE B

LOAD B

LINE C

LOAD C

VCOM

J2

A –

A +

B –

B +

C –

C +

+5 +15 VCOM

ICOM

Temp A

Temp B

Temp C

TEMP

DEFEAT

C

C

C

C

C

C

B

B

B

B

B

B

A

A

A

A

A

A

GATE

PULSE

ICOM

GATE

PULSE

GATE

PULSE

ROCKWELL

AUTOMATION

L N

TB6

SW2: When ON (up) provides

test pulses to gate driver circuits.

Note: Must be OFF (down) for

normal operation.

Phase A

Fibre Optic

Transmitters

send gate

signals to driver

boards

Phase B

Fibre Optic

Transmitters

Phase C

Fibre Optic

Transmitters

SW3: Used to defeat

temperature

feedback channels

Temperature

Feedback Fibre

Optics Receivers

Control Power

110…240V AC

Power Out

to SMC Flex

Serial
Number

Replacement
Part Number

LED (Yellow) ON
when Phase A gate
signal active

TP4: Phase A
gate signal

TP8: Common for
Gate/Pulse TPs

LED (Yellow) ON
when Phase B gate
signal active

TP11: Phase B
gate signal

LED (Yellow): ON
when Phase C gate
signal active

TP13: Phase C gate
signal

TP15: Common for
Gate/Pulse TPs

LEDs (Green): ON when signal
present at temperature feedback
fibre optic receivers

LED (Red): ON when test
pulses on.

SMC Flex Control Module

Ribbon connectors to connect to
SMC Flex Control Module
(underneath control module)

Current
feedback test
points

Ribbon connector
to Voltage Sensing
Board

Current loop
power supply
sensor input

TB5: Current
transformer
connections

TP18, 19, 20:
Power supply
test points

Voltage

feedback test

points

Module common:
Do not connect to

earth ground

LED (Green): ON

when current loop

power supply is

present

LED (Green): ON

when power is

present

Notes: 1. ICOM is the common connection for Gate and Pulse test points.

2. VCOM is the common connection for Current and Voltage feedback test points.

Do not connect J2 (VCOM) to earth ground; do not connect ICOM and VCOM together, either directly or
through test probes, meter or scope common.