Rockwell Automation 7763 Medium Voltage OneGear SMC Flex Motor Controller (10-15 kV) User Manual

Page 140

Advertising
background image

140

Rockwell Automation Publication 7760-UM001D-EN-P - October 2014

Appendix B

SMC Flex Module Parameter Information

Linear List

By-pass Delay

123

Sec

0…15

0

For applications that routinely see fast spikes of
current or overload conditions (more than 125% of
the SMC’s frame rating) this parameter can be used
to reduce the cycling between SCR and by-pass. This
time delay parameter will allow the SMC to stay
under SCR control for the duration of time
programmed.

Not applicable to
MV applications

Linear List

Fault 1

124

0…255

Fault buffer #1 allows display of the current fault. A
value of 0 indicates that there is no current fault.

Linear List

Fault 2

125

0…255

Fault buffer #2 represents fault history of the device
with fault #1 being the current fault and fault #5
being the oldest fault kept in memory.

Linear List

Fault 3

126

0…255

Fault buffer #3 represents fault history of the device
with fault #1 being the current fault and fault #5
being the oldest fault kept in memory.

Linear List

Fault 4

127

0…255

Fault buffer #4 represents fault history of the device
with fault #1 being the current fault and fault #5
being the oldest fault kept in memory.

Linear List

Fault 5

128

0…255

Fault buffer #5 represents fault history of the device
with fault #1 being the current fault and fault #5
being the oldest fault kept in memory.

Linear List

Ramp Time E

129

Sec

0…999

0

This parameter provides the user with the ability to
extend the ramp time beyond the initial range of 0-
30 seconds. To use this parameter, parameter 18
must be set to 0.

Linear List

Ramp Time 2E

130

Sec

0…999

0

Allows for the second ramp time to also be
extended. To use this parameter, parameter 26 must
be set to 0.

Linear List

Stop Time E

131

Sec

0…999

0

Allows the stop time be extended beyond the limit
of 120 seconds. Parameter 33 must be set to 0 for
this parameter to be active.

Basic Set Up

Option Input 1

132

Disable
Coast Stop
Option Fault
Fault NC
Network

Stop Option

Provides the user with the ability to define the
function of option Input #1.

Basic Set Up

Stop Input

133

Coast Stop
Option

Coast

Provides the user with the ability to define the
function of the stop input.

Linear List

Elapsed Time 2

134

Hours

0.0/3000.0

This is an additional Elapsed Time Meter that cannot
be reset by the user. It increments exactly as the
Elapsed Time but cannot be reset.

(1) Pump option modules default to “Pump Stop”.

(2) Brake option modules only.

Group

Parameter
Name

Parameter
Number

Units

Min./ Max.

Default Settings

Parameter Description

User Settings