Rockwell Automation 7763 Medium Voltage OneGear SMC Flex Motor Controller (10-15 kV) User Manual
Page 140
![background image](/manuals/580304/140/background.png)
140
Rockwell Automation Publication 7760-UM001D-EN-P - October 2014
Appendix B
SMC Flex Module Parameter Information
Linear List
By-pass Delay
123
Sec
0…15
0
For applications that routinely see fast spikes of
current or overload conditions (more than 125% of
the SMC’s frame rating) this parameter can be used
to reduce the cycling between SCR and by-pass. This
time delay parameter will allow the SMC to stay
under SCR control for the duration of time
programmed.
Not applicable to
MV applications
Linear List
Fault 1
124
0…255
Fault buffer #1 allows display of the current fault. A
value of 0 indicates that there is no current fault.
Linear List
Fault 2
125
0…255
Fault buffer #2 represents fault history of the device
with fault #1 being the current fault and fault #5
being the oldest fault kept in memory.
Linear List
Fault 3
126
0…255
Fault buffer #3 represents fault history of the device
with fault #1 being the current fault and fault #5
being the oldest fault kept in memory.
Linear List
Fault 4
127
0…255
Fault buffer #4 represents fault history of the device
with fault #1 being the current fault and fault #5
being the oldest fault kept in memory.
Linear List
Fault 5
128
0…255
Fault buffer #5 represents fault history of the device
with fault #1 being the current fault and fault #5
being the oldest fault kept in memory.
Linear List
Ramp Time E
129
Sec
0…999
0
This parameter provides the user with the ability to
extend the ramp time beyond the initial range of 0-
30 seconds. To use this parameter, parameter 18
must be set to 0.
Linear List
Ramp Time 2E
130
Sec
0…999
0
Allows for the second ramp time to also be
extended. To use this parameter, parameter 26 must
be set to 0.
Linear List
Stop Time E
131
Sec
0…999
0
Allows the stop time be extended beyond the limit
of 120 seconds. Parameter 33 must be set to 0 for
this parameter to be active.
Basic Set Up
Option Input 1
132
Disable
Coast Stop
Option Fault
Fault NC
Network
Stop Option
Provides the user with the ability to define the
function of option Input #1.
Basic Set Up
Stop Input
133
Coast Stop
Option
Coast
Provides the user with the ability to define the
function of the stop input.
Linear List
Elapsed Time 2
134
Hours
0.0/3000.0
This is an additional Elapsed Time Meter that cannot
be reset by the user. It increments exactly as the
Elapsed Time but cannot be reset.
(1) Pump option modules default to “Pump Stop”.
(2) Brake option modules only.
Group
Parameter
Name
Parameter
Number
Units
Min./ Max.
Default Settings
Parameter Description
User Settings