Starting Modes

Soft Start

This mode has the most general application. The motor is given an initial torque
setting, which is user-adjustable from 0…90% of locked-rotor torque. From the
initial torque level, the output voltage to the motor is steplessly increased during
the acceleration ramp time. The acceleration ramp time is user-adjustable from
0…30 seconds. Once the MV SMC Flex controller senses that the motor has
reached the up-to-speed condition during the voltage ramp operation, the output
voltage automatically switches to full voltage, and the bypass contactor is closed.

Figure 8 - Soft Start

100%

Percent
Voltage

Start

Run

Time (Seconds)

Initial