Status Indication
All auxiliary contacts can be programmed as NO or NC for the following states
except External Bypass, which can only be programmed as NO.
Normal/Normal NC:
The contact state changes when the unit receives a Start/
Stop signal.
Up-to-Speed/Up-to-Speed NC:
The contact state changes when the motor
approaches rated speed, and controls the Bypass switch for 7762 and 7763
configurations in
and
.
Alarm/Alarm NC:
The contact state changes when an Alarm condition is
detected.
Fault/Fault NC:
The contact state changes when a Fault condition is detected.
Network Control/Network Control NC:
The contact state is controlled over
the network. (Refer to
, which describes logic command
word to control auxiliary outputs.)
External Bypass:
This contact controls the Bypass switch for MV applications
with the 7760 configuration in
Note:
The tag name without a suffix indicates a NO state (e.g., Normal). On the
other hand, a tag name followed by NC indicates a normally close state (e.g.,
Normal NC).
Figure 21 - Control Terminals
Note:
•
The Aux #1 contact is always programmed Up-to-speed for 7762 and
7763 applications, or External Bypass (N.O.) for 7760 applications to
control the bypass circuit breaker/contactor.
•
The Aux #2 contact is typically programmed for fault indication (it can be
configured for N.O./N.C.).
•
The Aux #3 contact is typically programmed for alarm indication (it can
be configured for N.O./N.C.).
11
12
13
14
15
16
17
18
19
20
21
23
24
25
26
27
28
29
30
31
32
33
34
22
Opt
Input
#2
Opt
Input
#1
Start
Input
Stop
Input
Aux #1
(External
Bypass)
PTC
Input
TACH
Input
Ground
Fault
Aux #2
(Fault
Contract)
Aux #3
(Alarm
Contact)
Aux #4
(Normal)