Him control enable, Figure 38, Table 28 – Rockwell Automation 7763 Medium Voltage OneGear SMC Flex Motor Controller (10-15 kV) User Manual
Page 88
![background image](/manuals/580304/88/background.png)
88
Rockwell Automation Publication 7760-UM001D-EN-P - October 2014
Chapter 7
Communications
Figure 38 - SMC Flex Controller with Human Interface Module Connected
Table 28 - Description of Ports
HIM Control Enable
To enable motor control from a connected human interface module, follow the
procedure below with the connected human interface module’s programming
keys.
The Bulletin 20-HIM-LCD human interface modules with control panels can
start and stop the SMC FLEX controller. However, the factory default settings
disable control commands other than Stop through the serial communication
port.
To enable motor control from a connected human interface module or
communication module, you must take the following programming steps:
1.
Disconnect the HIM and allow to power down.
2.
Reconnect the HIM. On Initializing screen, the bottom right corner of
LCD shows Port X. Note this port number.
Port 5 – DPI Communications
Port 2
Ports 2 and 3 when two HIMs
are connected with a splitter
Port #
Description
1
Unused – Not available for use
2
First 20-HIM connected to SMC Flex
3
Second 20-HIM connected to SMC Flex
5
DPI Communication Board port