Chapter 7

Communications

Figure 38 - SMC Flex Controller with Human Interface Module Connected

Table 28 - Description of Ports

HIM Control Enable

To enable motor control from a connected human interface module, follow the
procedure below with the connected human interface module’s programming
keys.

The Bulletin 20-HIM-LCD human interface modules with control panels can
start and stop the SMC FLEX controller. However, the factory default settings
disable control commands other than Stop through the serial communication
port.

To enable motor control from a connected human interface module or
communication module, you must take the following programming steps:

1.

Disconnect the HIM and allow to power down.

2.

Reconnect the HIM. On Initializing screen, the bottom right corner of
LCD shows Port X. Note this port number.

Port 5 – DPI Communications

Port 2

Ports 2 and 3 when two HIMs

are connected with a splitter

Port #

Description

1

Unused – Not available for use

2

First 20-HIM connected to SMC Flex

3

Second 20-HIM connected to SMC Flex

5

DPI Communication Board port