Rockwell Automation Publication 7760-UM001D-EN-P - October 2014

139

SMC Flex Module Parameter Information

Appendix B

Linear List

I Shut Off

113

% current

0…37

0

This parameter adjusts the level of current at which
the SMC determines that the SCR has turned off.
Since this parameter has the potential to modify the
SCR control scheme, it is important that
adjustments be made with the help of Technical
Support.

Do not change
without factory
assistance.

Linear List

UTS Level

114

% up to
speed

0…100 75

The SMC has the ability to automatically determine
if the motor is up to speed. If there is a problem with
detecting the up-to-speed condition, this
parameter can be modified to compensate. Rule of
thumb is this number should be increased on high
efficiency motors experiencing problems. If the
SMC is detecting the up-to-speed condition too late
(or not at all) this number should be decreased on
very low efficiency motors. Note: Be careful when
adjusting this level. Improper adjustment can cause
the SMC to start at full voltage.

All Parameter

Mgmt

115

Ready Load
Default

Ready

Allows the user to load factory default values for all
parameters.

Basic Set Up

Backspin Timer

116

Secs

0…999

0

(Only available with the Pump Control option)
Ensures that a specific amount of time passes
between a stop and start sequence.

Linear List

V Shut Off Level

117

% V

0…100

25

This parameter provides the user with the ability to
manually adjust the level for the controller’s voltage
shut off detection. Since this parameter has the
potential to modify the SCR control scheme, it is
important that adjustments be made with the help
of Technical Support. It is important that you do not
disable both parameter 113 and this one at the
same time, otherwise SCR firing instability can
occur.

Linear List

OL Reset Level

118

%

0…99

75

Sets the level at which the motor overload is
allowed to be reset. Once the TCU% has dropped
below the program level, the device can be reset
manually or will auto reset if programmed for auto-
reset operation.

Linear List

Ambient
Temperature

119

0…60 50

Provides the ability to compensate for a lower or
higher ambient temperature condition. The
ambient temperature programmed should be
representative of the actual nominal temperature
(or worst case condition) since improper
programming can result in nuisance tripping or SCR
damage due to true SCR overheating.

Not applicable to
MV applications

Linear List

Notch Position

120

%

40.0…100.0

87.5

This parameter allows for the starting control
algorithm to be manually modified. It is
recommended that you do not make changes to this
parameter without specifically talking with
Technical Support.

Do not change

Linear List

Notch Maximum
(pump control)

121 50…70

70

This parameter allows for the pump stopping
control algorithm to be manually modified. It is
recommended that you do not make changes to this
parameter without specifically talking with
Technical Support.

Do not change

Linear List

Start Delay

122

Sec

0…30

0

An internal on-delay timer. Ensures that a
subsequent start can not be initiated for a preset
amount of time.

Group

Parameter
Name

Parameter
Number

Units

Min./ Max.

Default Settings

Parameter Description

User Settings