SMC Flex Module Parameter Information

Appendix B

Overload Overload

A

Lvl 50

%MTU 0…100 0

Allows the user to set an overload level (% of motor
thermal usage) that will cause an alarm when the
level exceeds the setting.

Underload Underload

F

Lvl 51

%FLC 0…99

0

Allows the user to set a current (% of line FLC) that
will cause a fault when the motor current falls
below this value. A zero value is the “off” setting.

Underload Underload

F

Dly 52

Secs

0…99

0

Allows the user the ability to prevent some nuisance
faults by entering a delay period that provides a
window that the motor current condition must
persist within for the controller to fault.

Underload

Underload A Lvl

53

%FLC

0…99

0

Allows the user to set a current (% of line FLC) that
will cause an Alarm when the motor current falls
below this value. A zero value is the “off” setting.

Underload

Underload A Dly

54

Secs

0…99

0

Allows the user the ability to prevent some nuisance
Alarm conditions by entering a delay period that
provides a window that the motor current condition
must persist within for the controller to Alarm.

Under-
voltage

Undervolt F Lvl

55

%V

0…99

0

Allows the user to set a voltage (% of line Voltage)
that will cause a fault when the voltage falls below
this value. A zero value is the “off” setting.

>80
recommended

Under-
voltage

Undervolt F Dly

56

Secs

0…99

0

Allows the user the ability to prevent some nuisance
faults by entering a delay period that provides a
window that the voltage condition must persist
within for the controller to fault.

1 sec
recommended

Under-
voltage

Undervolt A Lvl

57

%V

0…99

0

Allows the user to set a voltage (% of line Voltage)
that will cause an Alarm when the voltage falls
below this value. A zero value is the “off” setting.

Under-
voltage

Undervolt A Dly

58

Secs

0…99

0

Allows the user the ability to prevent some nuisance
Alarms by entering a delay period that provides a
window that the voltage condition must persist
within for the controller to Alarm.

Over-voltage Overvolt F Lvl

59

%V

0…199

0

Allows the user to set a voltage (% of line Voltage)
that will cause a fault when the voltage falls above
this value. A zero value is the “off” setting.

Over-voltage Overvolt F Dly

60

Secs

0…99

0

Allows the user the ability to prevent some nuisance
faults by entering a delay period that provides a
window that the voltage condition must persist
within for the controller to fault.

Over-voltage Overvolt

A

Lvl

61

%V

0…199

0

Allows the user to set a voltage (% of line Voltage)
that will cause an Alarm when the voltage falls
above this value. A zero value is the “off” setting.

Over-voltage Overvolt

A

Dly

62

Secs

0…99

0

Allows the user the ability to prevent some nuisance
Alarms by entering a delay period that provides a
window that the voltage condition must persist
within for the controller to Alarm.

Unbalance Unbalance

F

Lvl 63

%V

0…25

0

Allows the user to set a percentage of line to line
Voltages that will cause a fault when the voltage
falls above this value. A zero value is the “off”
setting.

Unbalance Unbalance

F

Dly 64

Secs

0…99

0

Allows the user the ability to prevent some nuisance
faults by entering a delay period that provides a
window that the voltage unbalance condition must
persist within for the controller to fault.

Unbalance

Unbalance A Lvl

65

%V

0…25

0

Allows the user to set a percentage of line to line
Voltages that will cause an Alarm when the voltage
falls above this value. A zero value is the “off”
setting.

Group

Parameter
Name

Parameter
Number

Units

Min./ Max.

Default Settings

Parameter Description

User Settings