Rockwell Automation 7763 Medium Voltage OneGear SMC Flex Motor Controller (10-15 kV) User Manual

Page 127

Advertising
background image

Rockwell Automation Publication 7760-UM001D-EN-P - October 2014

127

7760, 7761, 7762, and 7763 SMC Flex Specifications

Appendix A

Table 47 - Medium Voltage Magnetically Actuated Vacuum Circuit Breaker: 10…12 kV

Description

Specification

Voltage Ratings

(1)

Maximum Rated Voltage

12 kV

Basic Impulse Level (B.I.L.) Withstand– Phase to Ground, Phase to Phase (kV)

75

Rated Insulation Voltage

12 kV

Withstand Voltage at 50 Hz

28 kV

Frequency Ratings

50 / 60 Hz

Current Ratings

(1)

Rated Normal current (40 °C)

630 A

Rated Breaking Capacity (kA) (rated short-circuit breaking current symmetrical)

16, 20, 25, 31.5

Rated short-time withstand current (3s) (kA)

16, 20, 25, 31.5

Making Capacity (kA)

40, 50, 63, 80

Pole Distance (mm)

150

Opening Time (ms)

35…45

Arcing Time (ms)

10…15

Total Breaking Time (ms)

45…60

Closing Time (ms)

50…60

Operating Temperature (°C)

-25…50 (with derating)

(1) The voltage and current ratings listed are valid up to 1000 m (3300 feet). Please refer to Controller Derating chart for ratings above this altitude.

Advertising