Appendix A
7760, 7761, 7762, and 7763 SMC Flex Specifications
Table 48 - Medium Voltage Magnetically Actuated Vacuum Circuit Breaker: 12.5…15 kV
Description
Specification
Voltage Ratings
(1)
Maximum Rated Voltage
17.5 kV
Basic Impulse Level (B.I.L.) Withstand– Phase to Ground, Phase to Phase (kV)
95
Rated Insulation Voltage
17.5 kV
Withstand Voltage at 50 Hz
38 kV
Frequency Ratings
50 / 60 Hz
Current Ratings
Rated Normal current (40 °C)
630 A
Rated Breaking Capacity (kA) (rated short-circuit breaking current symmetrical)
16, 20, 25, 31.5
Rated short-time withstand current (3s) (kA)
16, 20, 25, 31.5
Making Capacity (kA)
40, 50, 63, 80
Pole Distance (mm)
150
Opening Time (ms)
35…45
Arcing Time (ms)
10…15
Total Breaking Time (ms)
45…60
Closing Time (ms)
50…60
Operating Temperature (°C)
-25…50 (with derating)