Rockwell Automation Publication 7760-UM001D-EN-P - October 2014
105
Troubleshooting
Chapter 8
Figure 43 - 14.4 kV Sensing Board Insulation Shrouds
6.
Replace with the new assembly securing with all 4 fasteners. (See diagram
below)
a. Reconnect the high voltage wire to the bus bars and plastic stand off
clips.
7.
Plug in ribbon cable making sure that it is positioned properly and fitting is
secure (locking mechanism is engaged). Re-connect both ground wires
and shield connection for the ribbon cable.
8.
For personnel and equipment safety, ensure both grounding connections
are reconnected to the sensing board.
Insulation Shroud
VSB channel
Nylon Screw goes here
ATTENTION: The high voltage wires must not touch earthed metal or bare
conductors.