Voltage sensing board testing – Rockwell Automation 7763 Medium Voltage OneGear SMC Flex Motor Controller (10-15 kV) User Manual

Page 112

Advertising
background image

112

Rockwell Automation Publication 7760-UM001D-EN-P - October 2014

Chapter 8

Troubleshooting

Voltage Sensing Board
Testing

1.

Check the resistance of the voltage sensing module (refer to

Figure 49

).

Remove the ribbon connector from J1 by pressing down on the locking
tabs then gently pulling the connector out. Measure the resistance between
each tap and the ground connection, and compare to the values in

Figure 49

. If the equipment includes an earthing switch, the board will be

effectively short-circuited to ground. In this case, remove the ground wires
before taking measurements.

Figure 49 - Voltage Sensing Board

Measure across R2, R4, R6, R10, R12, R14, R18, R20 and R22 located at the
bottom of each leg of the module. The resistance should be 11.3 kohm. (The two
ground connections must be connected to ground, or to each other if the module
has been removed.)

L1

T1

L2

T2

T3

L3

To Interface Board

Ground Connections

Rated

Voltage

12 kV

14.4 kV

Tap 1, 3, 5

to GND1

17.1 MΩ
22.2 MΩ

Tap 2, 4, 6

to GND1

25 MΩ

33.8 MΩ