Rockwell Automation 7763 Medium Voltage OneGear SMC Flex Motor Controller (10-15 kV) User Manual
Page 99
![background image](/manuals/580304/99/background.png)
Rockwell Automation Publication 7760-UM001D-EN-P - October 2014
99
Troubleshooting
Chapter 8
PTC Power Pole
10
• Controller ventilation blocked
• Controller duty cycle exceeded
• Fan failure
• Ambient temperature limit exceeded
• Failed thermistor
• Failed control module
• Failed gate driver board
• Failed fiber optic cable
• Failed interface board
• Check for proper ventilation
• Check application duty cycle
• Replace fan
• Wait for controller to cool or provide external cooling
• Check connection or replace thermistor
• Replace control module
• Test or replace gate driver board
• Test or replace cable
• Test or replace interface board or fiber optic board; check ribbon cables
Motor PTC
12
• Motor ventilation blocked
• Motor duty cycle exceeded
• PTC open
• Check for proper ventilation
• Check application duty cycle
• Wait for motor to cool or provide external cooling
• Check resistance of PTC
Open Bypass
13, 14, 15
• Control voltage is low
• Inoperable bypass contactor or breaker
• Check control voltage power supply
• Check control circuit operation
• Check control plug on contactor or breaker
• Check that Aux. 1 is set correctly (External bypass or up to speed as
required by the application. See
No load
16, 17, 18, 40
• Loss of load side power wiring
• Loss of feedback
• Check all load side power connections and motor windings
• Check voltage sensing module
Line Unbalance
19
• Supply unbalance is greater than the
user-programmed value
• The delay time is too short for the
application
• Unbalanced feedback
• Check power system and correct if necessary
• Extend the delay time to match the application requirements
• Check voltage sensing module
Overvoltage
20
• Supply voltage is greater than user-
programmed value
• Check power system and correct if necessary
• Correct the user-programmed value
Undervoltage
21
• Supply voltage is less than user-
programmed value
• The delay time is too short for the
application
• Check power system and correct if necessary
• Correct the user-programmed value
• Extend the delay time to match the application requirements.
Overload
22
• Motor overloaded
• Overload parameters are not matched
to the motor
• Check motor overload condition
• Check programmed values for overload class and motor FLC
Underload
23
• Broken motor shaft
• Broken belts, toolbits, etc.
• Pump cavitation
• Repair or replace motor
• Check machine
• Check pump system
Jam
24
• Motor current has exceeded the user
programmed jam level
• Correct source of jam
• Check programmed time value
Stall
25
• Motor has not reached full speed by the
end of the programmed ramp time
(plus Stall delay time)
• Correct source of stall
Phase Reversal
26
• Incoming supply voltage is not in the
expected ABC sequence
• Check power wiring
• Disable protection if not needed
Comm Loss
27, 28, 29
• Communication disconnection at the
serial port
• Check for a communication cable disconnection to the SMC Flex
controller
Network
30, 31, 32
• DPI network loss
• Reconnect for each DPI connected device
Ground Fault
33
• Ground fault current level has exceeded
programmed values
• Check power system and motor; correct if necessary
• Check programmed ground fault levels to match application
requirements
Excess Starts/Hr.
34
• Number of starts in a one-hour period
has exceeded the value programmed
• Wait an appropriate amount of time to restart
• Consult factory if more than 2 starts per hour are required
Power Loss (with phase
indication)
(1)
35, 36, 37
• Missing supply phase (as indicated)
• Loss of feedback
• Check for open line (i.e., blown line fuse)
• Check CT connections, replace Interface board
HAL_ID
38
• Faulty interface
• Check ribbon cable connections between interface board and control
module
• Replace interface board
Display
Fault Code
Possible Causes
Possible Solutions