Rockwell Automation Publication 7760-UM001D-EN-P - October 2014

99

Troubleshooting

Chapter 8

PTC Power Pole

10

Controller ventilation blocked
Controller duty cycle exceeded
Fan failure
Ambient temperature limit exceeded
Failed thermistor
Failed control module
Failed gate driver board
Failed fiber optic cable
Failed interface board

Check for proper ventilation
Check application duty cycle
Replace fan
Wait for controller to cool or provide external cooling
Check connection or replace thermistor
Replace control module
Test or replace gate driver board
Test or replace cable
Test or replace interface board or fiber optic board; check ribbon cables

Motor PTC

12

Motor ventilation blocked
Motor duty cycle exceeded
PTC open

Check for proper ventilation
Check application duty cycle
Wait for motor to cool or provide external cooling
Check resistance of PTC

Open Bypass

13, 14, 15

Control voltage is low
Inoperable bypass contactor or breaker

Check control voltage power supply
Check control circuit operation
Check control plug on contactor or breaker
Check that Aux. 1 is set correctly (External bypass or up to speed as

required by the application. See

Status Indication on page 38

.)

No load

16, 17, 18, 40

Loss of load side power wiring
Loss of feedback

Check all load side power connections and motor windings
Check voltage sensing module

Line Unbalance

19

Supply unbalance is greater than the

user-programmed value

The delay time is too short for the

application

Unbalanced feedback

Check power system and correct if necessary
Extend the delay time to match the application requirements
Check voltage sensing module

Overvoltage

20

Supply voltage is greater than user-

programmed value

Check power system and correct if necessary
Correct the user-programmed value

Undervoltage

21

Supply voltage is less than user-

programmed value

The delay time is too short for the

application

Check power system and correct if necessary
Correct the user-programmed value
Extend the delay time to match the application requirements.

Overload

22

Motor overloaded
Overload parameters are not matched

to the motor

Check motor overload condition
Check programmed values for overload class and motor FLC

Underload

23

Broken motor shaft
Broken belts, toolbits, etc.
Pump cavitation

Repair or replace motor
Check machine
Check pump system

Jam

24

Motor current has exceeded the user

programmed jam level

Correct source of jam
Check programmed time value

Stall

25

Motor has not reached full speed by the

end of the programmed ramp time
(plus Stall delay time)

Correct source of stall

Phase Reversal

26

Incoming supply voltage is not in the

expected ABC sequence

Check power wiring
Disable protection if not needed

Comm Loss

27, 28, 29

Communication disconnection at the

serial port

Check for a communication cable disconnection to the SMC Flex

controller

Network

30, 31, 32

DPI network loss

Reconnect for each DPI connected device

Ground Fault

33

Ground fault current level has exceeded

programmed values

Check power system and motor; correct if necessary
Check programmed ground fault levels to match application

requirements

Excess Starts/Hr.

34

Number of starts in a one-hour period

has exceeded the value programmed

Wait an appropriate amount of time to restart
Consult factory if more than 2 starts per hour are required

Power Loss (with phase
indication)

(1)

35, 36, 37

Missing supply phase (as indicated)
Loss of feedback

Check for open line (i.e., blown line fuse)
Check CT connections, replace Interface board

HAL_ID

38

Faulty interface

Check ribbon cable connections between interface board and control

module

Replace interface board

Display

Fault Code

Possible Causes

Possible Solutions