Control wiring – Rockwell Automation 7763 Medium Voltage OneGear SMC Flex Motor Controller (10-15 kV) User Manual

Page 80

Advertising
background image

80

Rockwell Automation Publication 7760-UM001D-EN-P - October 2014

Chapter 5

Options

Note:

Options that control the stopping of the motor (Soft Stop, Pump Stop,

Linear Speed, Braking) require the self-powered gate drivers to be pre-charged by
the current loop power supply. If this supply is not present, an alarm symbol will
appear at the upper right corner of the control module display, and the options
will be inhibited. When the motor is stopped, it will coast. If the supply is
restored, the alarm symbol will be cleared and the module will perform the
programmed sequence.

Control Wiring

Refer to

Chapter 1

for typical control wiring examples used with various control

schemes.

Slow Speed with Braking

SMC Option
This parameter identifies the type of control present and is not user
programmable.

Braking Control

Slow Speed Select
Allows the user to program the slow speed that best fits the
application.

Low:

7%

High:

15%

Slow Accel Current
Allows the user to program the required current to accelerate the
motor to slow speed operation.

0...450% of full load current

Slow Running Current
Allows the user to program the required current to operate the motor
at the slow speed setting.

0...450% of full load current

Braking Current
Allows the user to program the intensity of the braking current applied
to the motor.

0...400% of full load current

(1) Braking Control is not offered for standard use in MV applications. Please consult factory for further assistance.

(2) All braking/stopping current settings in the range of 1…100% will provide 100% braking current to the motor.

Option

Parameter

Range