Power factor correction capacitors – Rockwell Automation 7763 Medium Voltage OneGear SMC Flex Motor Controller (10-15 kV) User Manual

Page 18

Advertising
background image

18

Rockwell Automation Publication 7760-UM001D-EN-P - October 2014

Chapter 1

Product Overview

Power Factor Correction Capacitors

OneGear SMCs can be installed on a system with power factor correction
capacitors. These capacitors must be installed on the line side of the Power
Converter to prevent damage to the SMC Flex Controller silicon-controlled
rectifiers (SCR). A separate switching contactor or breaker is required for the
power factor correction capacitors. This switching device closes only after the
bypass contactor has closed. The power factor correction capacitors must also be
opened before the bypass contactor is opened to perform a stop function.

When discharged, a capacitor as essentially zero impedance. Therefore,
impedance must be added in series with the capacitors to limit inrush current.

Acceptable optional PFCC connection methods for Bulletin 7760, 7762, and
7763 are shown in

Figure 5

,

Figure 6

, and

Figure 7

. The same concept applies to

Bulletin 7761.

Figure 5 - Typical OneGear Single Line Diagram Bulletin 7760 (10…14.4 kV) with two optional
Power Factor Correction Capacitor positions (Vacuum Breaker)

TIP

Consult the factory is there are capacitors on the same branch circuit as the
OneGear SMC.

WARNING: Do not connect power factor correction capacitors in the circuit
when OneGear SMC SCRs are gating.

Power Converter

Bypass Controller

Optional PFCC

Breaker

Fused
Contactor

PFCC

SMC Flex
Control
Module

R, S, T

R, S, T

R, S, T

R, S, T

U, V, W

M

R, S, T

R, S, T

Fused
Contactor

PFCC

Optional PFCC

Cable Connection Point

Existing Controller

Breaker

Optional
Earthing
Switch

Advertising