Rockwell Automation 7763 Medium Voltage OneGear SMC Flex Motor Controller (10-15 kV) User Manual
Page 132
![background image](/manuals/580304/132/background.png)
132
Rockwell Automation Publication 7760-UM001D-EN-P - October 2014
Appendix B
SMC Flex Module Parameter Information
Basic Set Up
Line Voltage
16
V
0…15,000
480
This parameter sets the base voltage for the under /
over voltage protective features. For medium
voltage applications the controller has internal
capabilities set of multipliers that correspond to the
line voltage dividers.
Basic Set Up
Starting Mode
17
Full Voltage
Current Limit
Soft Start
Linear
Speed Pump
Start
Soft Start
Allows the user to select the type of start provided
with controller configuration.
Basic Set Up
Ramp Time
18
Secs
0…30
10
Allows the user to program the time (0…30 s) that
the controller performs the starting maneuver. The
starting maneuver will automatically transition to
bypass and full voltage if the controller senses that
the motor has reached full speed prior to the ramp
time completion. Also refer to Parameter 129.
Basic Set Up
Initial Torque
19
%LRT
0…90
70
When using the soft start mode, this parameter
allows the user to adjust the initial torque level
applied to the motor at the beginning of the start
maneuver.
Basic Set Up
Cur Limit Start
Level
20 %FLC
50…600
350
When using the current limit starting mode, this
parameter allows the user to adjust the current level
applied to the motor during the start maneuver.
Basic Set Up
Reserved
21
Reserved
Basic Set Up
Kickstart Time
22
Secs
0.0…2.0
0.0
When programmed with a non-zero value, this
parameter provides a torque pulse for the
programmed time period at the beginning of the
starting maneuver (0.0…2.0 s).
Basic Set Up
Kickstart Level
23
%LRT
0…90
0
When the Kickstart Time is programmed, this
parameter provides the user with the ability to set
the level of the torque pulse applied to the motor
(approx. 0…90%).
Basic Set Up
Option Input 2
24
Disable Preset
Slow Speed
Dual Ramp
Fault Fault NC
Network Clear
Fault
Disable
Provides the user with the ability to define the
function of option Input #2 (disable, coast, stop
option, fault, fault N.C., network).
Dual Ramp
Starting Mode 2
25
Full Voltage
Current Limit
Soft Start
Linear
Speed Pump
Start
Soft Start
When the dual ramp mode is selected, this
parameter allows the user to select the type of ramp
mode used for the second ramp profile.
Dual Ramp
Ramp Time 2
26
Secs
0…30
10
When the dual ramp mode is selected, this
parameter allows the user to program the time
(0…30 s) that the controller performs the starting
maneuver for profile #2. Also refer to Parameter
130.
Dual Ramp
Initial Torque 2
27
%LRT
0…90
70
When using the soft start mode for profile #2, this
parameter allows the user to adjust the initial
torque level applied to the motor at the beginning
of the start maneuver.
Dual Ramp
Cur Limit Level 2
28
%FLC
50…600
350
When using the current limit starting mode for
profile #2, this parameter allows the user to adjust
the current level applied to the motor during the
start maneuver.
Group
Parameter
Name
Parameter
Number
Units
Min./ Max.
Default Settings
Parameter Description
User Settings