Rockwell Automation 7763 Medium Voltage OneGear SMC Flex Motor Controller (10-15 kV) User Manual

Page 132

Advertising
background image

132

Rockwell Automation Publication 7760-UM001D-EN-P - October 2014

Appendix B

SMC Flex Module Parameter Information

Basic Set Up

Line Voltage

16

V

0…15,000

480

This parameter sets the base voltage for the under /
over voltage protective features. For medium
voltage applications the controller has internal
capabilities set of multipliers that correspond to the
line voltage dividers.

Basic Set Up

Starting Mode

17

Full Voltage
Current Limit
Soft Start
Linear
Speed Pump
Start

Soft Start

Allows the user to select the type of start provided
with controller configuration.

Basic Set Up

Ramp Time

18

Secs

0…30

10

Allows the user to program the time (0…30 s) that
the controller performs the starting maneuver. The
starting maneuver will automatically transition to
bypass and full voltage if the controller senses that
the motor has reached full speed prior to the ramp
time completion. Also refer to Parameter 129.

Basic Set Up

Initial Torque

19

%LRT

0…90

70

When using the soft start mode, this parameter
allows the user to adjust the initial torque level
applied to the motor at the beginning of the start
maneuver.

Basic Set Up

Cur Limit Start
Level

20 %FLC

50…600

350

When using the current limit starting mode, this
parameter allows the user to adjust the current level
applied to the motor during the start maneuver.

Basic Set Up

Reserved

21

Reserved

Basic Set Up

Kickstart Time

22

Secs

0.0…2.0

0.0

When programmed with a non-zero value, this
parameter provides a torque pulse for the
programmed time period at the beginning of the
starting maneuver (0.0…2.0 s).

Basic Set Up

Kickstart Level

23

%LRT

0…90

0

When the Kickstart Time is programmed, this
parameter provides the user with the ability to set
the level of the torque pulse applied to the motor
(approx. 0…90%).

Basic Set Up

Option Input 2

24

Disable Preset
Slow Speed
Dual Ramp
Fault Fault NC
Network Clear
Fault

Disable

Provides the user with the ability to define the
function of option Input #2 (disable, coast, stop
option, fault, fault N.C., network).

Dual Ramp

Starting Mode 2

25

Full Voltage
Current Limit
Soft Start
Linear
Speed Pump
Start

Soft Start

When the dual ramp mode is selected, this
parameter allows the user to select the type of ramp
mode used for the second ramp profile.

Dual Ramp

Ramp Time 2

26

Secs

0…30

10

When the dual ramp mode is selected, this
parameter allows the user to program the time
(0…30 s) that the controller performs the starting
maneuver for profile #2. Also refer to Parameter
130.

Dual Ramp

Initial Torque 2

27

%LRT

0…90

70

When using the soft start mode for profile #2, this
parameter allows the user to adjust the initial
torque level applied to the motor at the beginning
of the start maneuver.

Dual Ramp

Cur Limit Level 2

28

%FLC

50…600

350

When using the current limit starting mode for
profile #2, this parameter allows the user to adjust
the current level applied to the motor during the
start maneuver.

Group

Parameter
Name

Parameter
Number

Units

Min./ Max.

Default Settings

Parameter Description

User Settings