Rockwell Automation 7763 Medium Voltage OneGear SMC Flex Motor Controller (10-15 kV) User Manual

Page 129

Advertising
background image

Rockwell Automation Publication 7760-UM001D-EN-P - October 2014

129

7760, 7761, 7762, and 7763 SMC Flex Specifications

Appendix A

Table 49 - Medium Voltage Vacuum Contactor: 10 to 12 kV

Description

Specification

Voltage Ratings

(1)

Maximum Rated Voltage

12 kV

Rated insulation voltage

12 kV

Impulse withstand voltage

75 kV

Withstand Voltage at 50 Hz

28 kV

Frequency Ratings

50 / 60 Hz

Current Ratings

(1)

Rated service current

A

400

Rated normal current

A

400

Short-time withstand current for 1 s

A

6000

Rated Peak Current

kA

15

Rated short-circuit time

S

1

Maximum rated admissible overcurrent for ½ period (peak
value)

kA

55

Rated load and overload characteristics in category of use:

Category AC4) 100 closing operations (A)

4000

Category AC4) 25 opening operations (A)

4000

Electrical Life at rated current verified as in Category AC1

Operations

1000000

Mechanical Life

Operations

1000000

Short-circuit breaking capacity (O…3min-CO…3min-CO)

(A)

4000

Short-circuit making capacity (O…3min-CO-3min…CO)

(A) Peak

8000

Switching Times

Opening Time (lower and upper limit) (ms)

20…30

Closing Time (lower and upper limit) (ms)

30…50

Relative Humidity, without condensation

%

<95

Operating Temperature

°C

-5…50 (with derating)

(1) The voltage and current ratings listed are valid up to 1000 m (3300 feet). Please refer to Controller Derating chart for ratings above this altitude.

Advertising