7760, 7761, 7762, and 7763 SMC Flex Specifications
Appendix A
Table 49 - Medium Voltage Vacuum Contactor: 10 to 12 kV
Description
Specification
Voltage Ratings
(1)
Maximum Rated Voltage
12 kV
Rated insulation voltage
12 kV
Impulse withstand voltage
75 kV
Withstand Voltage at 50 Hz
28 kV
Frequency Ratings
50 / 60 Hz
Current Ratings
Rated service current
A
400
Rated normal current
A
400
Short-time withstand current for 1 s
A
6000
Rated Peak Current
kA
15
Rated short-circuit time
S
1
Maximum rated admissible overcurrent for ½ period (peak
value)
kA
55
Rated load and overload characteristics in category of use:
Category AC4) 100 closing operations (A)
4000
Category AC4) 25 opening operations (A)
4000
Electrical Life at rated current verified as in Category AC1
Operations
1000000
Mechanical Life
Operations
1000000
Short-circuit breaking capacity (O…3min-CO…3min-CO)
(A)
4000
Short-circuit making capacity (O…3min-CO-3min…CO)
(A) Peak
8000
Switching Times
Opening Time (lower and upper limit) (ms)
20…30
Closing Time (lower and upper limit) (ms)
30…50
Relative Humidity, without condensation
%
<95
Operating Temperature
°C
-5…50 (with derating)