Rockwell Automation Publication 7760-UM001D-EN-P - October 2014

Appendix B

SMC Flex Module Parameter Information

Basic Set Up

Aux1 Config

107

Normal
Normal NC
Up To Speed
Up To Speed
NC Fault Fault
NC Alarm
Alarm NC
Network
Network NC
External
Bypass

Normal

Allows the user the ability to configure each
Auxiliary relay contact for a specific operation
Note: Normal = SMC in RUN

External Bypass or
Up-to-Speed (see
Chap. 1)

Basic Set Up

Aux3 Config

108

Normal
Normal NC
Up To Speed
Up To Speed
NC Fault Fault
NC Alarm
Alarm NC
Network
Network NC
External
Bypass

Alarm

Allows the user the ability to configure each
Auxiliary relay contact for a specific operation
Note: Normal = SMC in RUN

Basic Set Up

Aux4 Config

109

Normal
Normal NC
Up To Speed
Up To Speed
NC Fault Fault
NC Alarm
Alarm NC
Network
Network NC
External
Bypass

Normal

Allows the user the ability to configure each
Auxiliary relay contact for a specific operation
Note: Normal = SMC in RUN

Basic Set Up

Aux2 Config

110

Normal
Normal NC
Up To Speed
Up To Speed
NC Fault Fault
NC Alarm
Alarm
NC Network
Network NC
External
Bypass

Fault

Allows the user the ability to configure each
Auxiliary relay contact for a specific operation
Note: Normal = SMC in RUN

Language Language

111

English
French
Spanish
German
Portuguese
Mandarin

English

Allows the user to change the text display to one of
the available options.

Linear List

Timed Start

112

0 = Disable
1=Enable

Disable

This parameter can be used to force the starting
profile to complete its entire time period and ignore
an early up-to-speed detection. The default is set to
“Disabled”, so that the SMC can determine when the
motor is at speed.

See parameter 114
before adjusting
this parameter.

Group

Parameter
Name

Parameter
Number

Units

Min./ Max.

Default Settings

Parameter Description

User Settings