Appendix B
SMC Flex Module Parameter Information
Basic Set Up
Aux1 Config
107
Normal
Normal NC
Up To Speed
Up To Speed
NC Fault Fault
NC Alarm
Alarm NC
Network
Network NC
External
Bypass
Normal
Allows the user the ability to configure each
Auxiliary relay contact for a specific operation
Note: Normal = SMC in RUN
External Bypass or
Up-to-Speed (see
Chap. 1)
Basic Set Up
Aux3 Config
108
Normal
Normal NC
Up To Speed
Up To Speed
NC Fault Fault
NC Alarm
Alarm NC
Network
Network NC
External
Bypass
Alarm
Allows the user the ability to configure each
Auxiliary relay contact for a specific operation
Note: Normal = SMC in RUN
Basic Set Up
Aux4 Config
109
Normal
Normal NC
Up To Speed
Up To Speed
NC Fault Fault
NC Alarm
Alarm NC
Network
Network NC
External
Bypass
Normal
Allows the user the ability to configure each
Auxiliary relay contact for a specific operation
Note: Normal = SMC in RUN
Basic Set Up
Aux2 Config
110
Normal
Normal NC
Up To Speed
Up To Speed
NC Fault Fault
NC Alarm
Alarm
NC Network
Network NC
External
Bypass
Fault
Allows the user the ability to configure each
Auxiliary relay contact for a specific operation
Note: Normal = SMC in RUN
Language Language
111
English
French
Spanish
German
Portuguese
Mandarin
English
Allows the user to change the text display to one of
the available options.
Linear List
Timed Start
112
0 = Disable
1=Enable
Disable
This parameter can be used to force the starting
profile to complete its entire time period and ignore
an early up-to-speed detection. The default is set to
“Disabled”, so that the SMC can determine when the
motor is at speed.
See parameter 114
before adjusting
this parameter.
Group
Parameter
Name
Parameter
Number
Units
Min./ Max.
Default Settings
Parameter Description
User Settings