Rockwell Automation 7763 Medium Voltage OneGear SMC Flex Motor Controller (10-15 kV) User Manual
Page 137
![background image](/manuals/580304/137/background.png)
Rockwell Automation Publication 7760-UM001D-EN-P - October 2014
137
SMC Flex Module Parameter Information
Appendix B
Restart Restart
Delay 83
Secs 0…60 0
Provides a delay time between restart attempts to
allow for the condition to be removed.
Linear List
Line Fault Disable
84
0=Disable
1=Disable F1
2=DisableF41
3=Enable
Enable
This parameter gives the user the ability to
selectively disable specific fault codes such as F1, F2,
F3 and F41, F42, F43. These faults are used to detect
problems with incoming power and the detection of
appropriate zero crosses (F1) or the firing of the
SCRs based on the current and voltage
characteristics associated with the SCR turning off
(F41). These faults can only occur during starting or
stopping and are usually related to the incoming
power condition.
Linear List
Emergency Run
85
0 = Disable
1=Enable
Disable
This parameter defeats all running faults and is only
effective in the “run” mode. It will not override
faults prior to starting (i.e. shorted SCR). This
parameter is reset to “off/disable” when control
power is recycled.
Linear List
Current Loss
86
0 = Disable
1=Enable
Enable
This parameter allows the user to override a current
loss fault. This is indicative of the typical failure
mode of a damaged CT.
Comm Masks Logic Mask
87
8-bit binary
0
Allows the user to enable or disable control from
various serial interface ports (DPI) with a “0”
setting. If a port is set to “1”, the port will be
allowed to control the SMC and will produce a
comm. fault if disconnected.
DataLinks
Data In A1
88
0
16 bit Datalink
DataLinks
Data In A2
89
0
16 bit Datalink
DataLinks
Data In B1
90
0
16 bit Datalink
DataLinks
Data In B2
91
0
16 bit Datalink
DataLinks
Data In C1
92
0
16 bit Datalink
DataLinks
Data In C2
93
0
16 bit Datalink
DataLinks
Data In D1
94
0
16 bit Datalink
DataLinks
Data In D2
95
0
16 bit Datalink
DataLinks
Data Out A1
96
0
16 bit Datalink
DataLinks
Data Out A2
97
0
16 bit Datalink
DataLinks
Data Out B1
98
0
16 bit Datalink
DataLinks
Data Out B2
99
0
16 bit Datalink
DataLinks
Data Out C1
100
0
16 bit Datalink
DataLinks
Data Out C2
101
0
16 bit Datalink
DataLinks
Data Out D1
102
0
16 bit Datalink
DataLinks
Data Out D2
103
0
16 bit Datalink
Motor Data
Motor ID
104
0…65535
0
Allows the user the ability to assign a specific
identification number to a motor and controller
combination. This can be useful for network
applications where you may need to locate a specific
motor/controller based on a network address.
Motor Data
CT Ratio
105
1…1500
Sets the proper current ratio when an external
current transformer is used for Medium Voltage
applications. (example, for 150:5, set 150)
Motor Data
MV Ratio
106
1…10000
Sets the proper feedback scaling when used for
Medium Voltage applications.
See
Group
Parameter
Name
Parameter
Number
Units
Min./ Max.
Default Settings
Parameter Description
User Settings