Rockwell Automation 7763 Medium Voltage OneGear SMC Flex Motor Controller (10-15 kV) User Manual

Page 137

Advertising
background image

Rockwell Automation Publication 7760-UM001D-EN-P - October 2014

137

SMC Flex Module Parameter Information

Appendix B

Restart Restart

Delay 83

Secs 0…60 0

Provides a delay time between restart attempts to
allow for the condition to be removed.

Linear List

Line Fault Disable

84

0=Disable
1=Disable F1
2=DisableF41
3=Enable

Enable

This parameter gives the user the ability to
selectively disable specific fault codes such as F1, F2,
F3 and F41, F42, F43. These faults are used to detect
problems with incoming power and the detection of
appropriate zero crosses (F1) or the firing of the
SCRs based on the current and voltage
characteristics associated with the SCR turning off
(F41). These faults can only occur during starting or
stopping and are usually related to the incoming
power condition.

Linear List

Emergency Run

85

0 = Disable
1=Enable

Disable

This parameter defeats all running faults and is only
effective in the “run” mode. It will not override
faults prior to starting (i.e. shorted SCR). This
parameter is reset to “off/disable” when control
power is recycled.

Linear List

Current Loss

86

0 = Disable
1=Enable

Enable

This parameter allows the user to override a current
loss fault. This is indicative of the typical failure
mode of a damaged CT.

Comm Masks Logic Mask

87

8-bit binary

0

Allows the user to enable or disable control from
various serial interface ports (DPI) with a “0”
setting. If a port is set to “1”, the port will be
allowed to control the SMC and will produce a
comm. fault if disconnected.

DataLinks

Data In A1

88

0

16 bit Datalink

DataLinks

Data In A2

89

0

16 bit Datalink

DataLinks

Data In B1

90

0

16 bit Datalink

DataLinks

Data In B2

91

0

16 bit Datalink

DataLinks

Data In C1

92

0

16 bit Datalink

DataLinks

Data In C2

93

0

16 bit Datalink

DataLinks

Data In D1

94

0

16 bit Datalink

DataLinks

Data In D2

95

0

16 bit Datalink

DataLinks

Data Out A1

96

0

16 bit Datalink

DataLinks

Data Out A2

97

0

16 bit Datalink

DataLinks

Data Out B1

98

0

16 bit Datalink

DataLinks

Data Out B2

99

0

16 bit Datalink

DataLinks

Data Out C1

100

0

16 bit Datalink

DataLinks

Data Out C2

101

0

16 bit Datalink

DataLinks

Data Out D1

102

0

16 bit Datalink

DataLinks

Data Out D2

103

0

16 bit Datalink

Motor Data

Motor ID

104

0…65535

0

Allows the user the ability to assign a specific
identification number to a motor and controller
combination. This can be useful for network
applications where you may need to locate a specific
motor/controller based on a network address.

Motor Data

CT Ratio

105

1…1500

Sets the proper current ratio when an external
current transformer is used for Medium Voltage
applications. (example, for 150:5, set 150)

Motor Data

MV Ratio

106

1…10000

Sets the proper feedback scaling when used for
Medium Voltage applications.

See

Table 6

Group

Parameter
Name

Parameter
Number

Units

Min./ Max.

Default Settings

Parameter Description

User Settings