Motor protection – Rockwell Automation 7763 Medium Voltage OneGear SMC Flex Motor Controller (10-15 kV) User Manual
Page 72
72
Rockwell Automation Publication 7760-UM001D-EN-P - October 2014
Chapter 3
Programming
Motor Protection
While the Basic Set Up group allows the user to get started with a minimum
number of parameters to modify, the Motor Protection group allows full access
to the SMC Flex controller's powerful parameter set. Following is a listing of the
additional setup parameters provided.
Note:
The majority of parameters have a Fault and an Alarm setting.
Table 20 - Motor Protection Parameters and Options
Aux1 Config
(3)
Contact is provided as standard with the SMC Flex controller. This contact is located at terminals 19 and
20. Aux Contacts 1 allows the user to configure the operation of the contacts.
Normal, Normal NC, Up-to-Speed, Up-
to-Speed NC, Fault, Fault NC, Alarm,
Alarm NC, Network, Network NC,
External Bypass
Aux2 Config
Contact is provided as standard with the SMC Flex controller. This contact is located at terminals 29 and
30. Aux Contacts 2 allows the user to configure the operation of the contacts.
Normal, Normal NC, Up-to-Speed, Up-
to-Speed NC, Fault, Fault NC, Alarm,
Alarm NC, Network, Network NC,
External Bypass
Aux3 Config
Contact is provided as standard with the SMC Flex controller. This contact is located at terminals 31 and
32. Aux Contacts 3 allows the user to configure the operation of the contacts.
Normal, Normal NC, Up-to-Speed, Up-
to-Speed NC, Fault, Fault NC, Alarm,
Alarm NC, Network, Network NC,
External Bypass
Aux4 Config
Contact is provided as standard with the SMC Flex controller. This contact is located at terminals 33 and
34. Aux Contacts 4 allows the user to configure the operation of the contacts.
Normal, Normal NC, Up-to-Speed, Up-
to-Speed NC, Fault, Fault NC, Alarm,
Alarm NC, Network, Network NC,
External Bypass
Parameter Mgmt
Recall of factory default parameter values.
Ready, Load Default
(1) Starting Mode must be programmed to Soft Start to obtain access to the Initial Torque parameter.
(2) Starting Mode must be programmed to Current Limit to obtain access to the Current Limit Level parameter.
(3) Refer to the I/O section on
and Notes on
for MV specific functionality.
(4) This is not to indicate how the motor windings are configured. Do not select "Delta" for MV applications.
(5) When programmed for 'Emergency Run' and the Option 2 input is energized, a 'Start' command will first close the bypass contactor, then the line contactor for an across-the-line start of the motor. A
'Stop' command will open the line contactor first and allow the motor to coast, regardless of the programmed 'Stop Mode'. For Pump Option modules, the Option 2 input defaults to 'Emergency Run' for
MV applications.
Parameter
Description
Option
Parameter
Description
Option
Overload
Allows the user to select the operation of the overload.
Trip Class, Service Factor, Motor FLC,
Overload Reset, Overload Alarm Level
Underload
(1)(2)
Determines the trip level as a percentage of the motor's FLA, and the delay period.
Underload Fault Level, Underload Fault
Delay, Underload Alarm Level,
Underload Alarm Delay
Undervoltage
Determines the trip level as a percentage of line voltage and delay period.
Undervoltage Fault Level, Undervoltage
Fault Delay, Undervoltage Alarm Level,
Undervoltage Alarm Delay
Overvoltage
Determines the trip level as a percentage of line voltage and delay period.
Overvoltage Fault Level, Overvoltage
Fault Delay, Overvoltage Alarm Level,
Overvoltage Alarm Delay
Unbalance
Allows the user to set the current unbalance trip level and delay period.
Unbalance Fault Level, Unbalance Fault
Delay, Unbalance Alarm Level,
Unbalance Alarm Delay
Jam
Determines the trip level as a percentage of motor full load current and delay period.
Jam Fault Level, Jam Fault Delay, Jam
Alarm Level, Jam Alarm Delay
Stall
Allows the user to set the stall delay time.
Stall Delay