Rockwell Automation 7763 Medium Voltage OneGear SMC Flex Motor Controller (10-15 kV) User Manual

Page 109

Advertising
background image

Rockwell Automation Publication 7760-UM001D-EN-P - October 2014

109

Troubleshooting

Chapter 8

If the power pole resistance is a multiple of 25 k lower than specified above, there
may be one or more shorted SCRs in the PowerBricks.

3.

If a short circuit is suspected, the power pole cart must be removed from
the equipment to facilitate further testing. Refer to cart removal
instructions in the Installation Instructions Manual (publication

7760-IN001_-EN-P

).

4.

Remove the clear plastic guards from the front and rear of the power pole
assembly by removing two screws from the top and bottom of each guard.

5.

Measure DC resistances as follows for each PowerBrick: (Refer to

Figure 46

).

C1 to C2:

21…29 k

Gate to Cathode (G/C):

4…40

Figure 46 - PowerBrick Current Loop Gate Driver Board Connections

6.

If the resistance values are out of range, the PowerBrick must be removed
from the power pole cart assembly. Refer to PowerBrick removal procedure
in the Installation Manual (publication

7760-IN001_-EN-P

).

CT

J1

Therm

Rx1 Tx1

CT

J2

Rx2 Tx2

Connection to H3

Snubber Capacitor

Connection

Connection to H2

Snubber Resistor

Connection

Current Loop

CT Connector

Test Power Supply

Connector

Gate Logic Fibre Optic Receiver

Temperature Feedback Fibre Optic Transmitter

Thermistor Connector (J2)

Match Band Character

SCR Gate Lead
Connectors (J5)

Overvoltage Sense Connection

Advertising