Options

Chapter 5

Programming Parameters

The following table provides the option-specific parameters that are provided
with each control option. These parameters are in addition to those already
discussed in the Basic Set Up and Metering groups. Diagrams supporting the
options described below are shown later in this chapter.

Option

Parameter

Range

Pump Control

Pump Control

SMC Option
This parameter identifies the type of control present and is not user
programmable.

Pump Control

Pump Stop Time
Allows the user to set the time period for the pump stopping function.

0...120 s

Starting Mode
Allows the user to program the SMC-Flex controller for the type of
starting that best fits the application.

Pump Start, Soft Start, Current Limit Start, Full Voltage

Braking Control

(1)

SMB Smart Motor Braking

SMC Option
This parameter identifies the type of control present and is not user
programmable.

Braking Control

Braking Current

(2)

Allows the user to program the intensity of the braking current applied
to the motor.

0…400% of full load current

Accu-Stop

SMC Option
This parameter identifies the type of control present and is not user
programmable.

Braking Control

Slow Speed Select
Allows the user to program the slow speed that best fits the
application.

Low:

7%

High:

15%

Slow Accel Current
Allows the user to program the required current to accelerate the
motor to slow speed operation.

0...450% of full load current

Slow Running Current
Allows the user to program the required current to operate the motor
at slow speed operation.

0...400% of full load current

Braking Current
Allows the user to program the intensity of the braking current applied
to the motor.

0...400% of full load current

Stopping Current
Allows the user to program the intensity of the braking current applied
to the motor from slow speed operation.

0...400% of full load current