Proposal for Implementation of Power Factor Correction Capacitors

1.

Normal start rung, KG1 initiates start through the SMC Flex module at
Term 16.

2.

M closes, motor accelerates, the Up to Speed contact within the SMC Flex
module between terminal 19 and 20 closes, B closes.

3.

B, KG3 and KG1 then close KG4 to apply PFCC.

4.

If option stop, KG1 opens KG4 immediately to drop out PFCC, and
command SMC to stop.

5.

CC holds in B until CC drops out, then permits B to open, option stop
continues.

6.

If a coast stop is initiated, the Flex will open the contact between 20 and
34; KG3 will open M and command KG4 to open CC. CC will hold B
until CC drops out.

Permissives

Option

Stop

Coast

Stop

Control Relay

Bypass Control (B)

Start Control (M)

Capacitor
Control (CC)

MPR

KG1

B

KG3

KG1

Start

KG3

KG1

KG1

KG2

KG3

KG4

SMC Flex Control Module

CC