Chapter 1
Product Overview
Proposal for Implementation of Power Factor Correction Capacitors
1.
Normal start rung, KG1 initiates start through the SMC Flex module at
Term 16.
2.
M closes, motor accelerates, the Up to Speed contact within the SMC Flex
module between terminal 19 and 20 closes, B closes.
3.
B, KG3 and KG1 then close KG4 to apply PFCC.
4.
If option stop, KG1 opens KG4 immediately to drop out PFCC, and
command SMC to stop.
5.
CC holds in B until CC drops out, then permits B to open, option stop
continues.
6.
If a coast stop is initiated, the Flex will open the contact between 20 and
34; KG3 will open M and command KG4 to open CC. CC will hold B
until CC drops out.
Permissives
Option
Stop
Coast
Stop
Control Relay
Bypass Control (B)
Start Control (M)
Capacitor
Control (CC)
MPR
KG1
B
KG3
KG1
Start
KG3
KG1
KG1
KG2
KG3
KG4
SMC Flex Control Module
CC