12 kv voltage sensing board (vsb), 4 kv voltage sensing board (vsb) – Rockwell Automation 7763 Medium Voltage OneGear SMC Flex Motor Controller (10-15 kV) User Manual

Page 104

Advertising
background image

104

Rockwell Automation Publication 7760-UM001D-EN-P - October 2014

Chapter 8

Troubleshooting

12 kV Voltage Sensing Board (VSB)

a. Place the assembly on a flat surface (table or bench) and disconnect the

wires from the six channels at the end of the VSB. Cut the cable ties and
remove the wires from the assembly.

b. Install the wires on the new assembly in the same positions and secure

them with cable ties at the ends of the wire guide channels.

Figure 42 - Sensing Board High Voltage Wire Connections

14.4 kV Voltage Sensing Board (VSB)

c. Place the assembly on a flat surface (table or bench).
d. Remove the nylon screws that secure the insulation shrouds from the

ends of the VSB channels, and remove the shrouds.

e. Disconnect the wires from the six channels at the end of the VSB. Cut

the cable ties and remove the wires from the assembly.

f. Install the wires on the new assembly in the same positions and secure

them with cable ties at the ends of the wire guide channels.

g. Re-install the insulation shrouds with nylon screws, torque to 0.3 N•m

(2.7 lb•in).

Mounting Hardware

Cable Ties

Mounting Hardware

Wire Guide Channels

High Voltage Wires

ATTENTION: The insulation shrouds are required to prevent insulation
breakdowns due to surge voltages. Failure to replace all six covers with nylon
hardware before energizing may result in personal injury, property damage or
economic loss.

Advertising